![TCL u Series Operation Manual Download Page 6](http://html1.mh-extra.com/html/tcl/u-series/u-series_operation-manual_824568006.webp)
5
z
Optional Spec.
Model u
M
uTC52 uTC62 uTC72 uTC42 uTC92
Output 2
For heating and cooling control use.
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
SPST type
SPDT type
SPST type
SPDT type
SPDT type
Alarm 2
3A , 220V , electrical life:100,000 times or more (under rated load)
Available Available Available Available
Not
available
SPST type
SPST type
SPST type
SPST type
Alarm 3
3A , 220V , electrical life:100,000 times or more (under rated load)
Display range of heater current : 0.0~99.9A , Accuracy : 1%FS
Included CT : SC-80-T
Heater Break Alarm
(HBA)
Alarm relay : AL1
Available for PV or SV transmission
Transmission
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Remote SV
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Protocol : MODBUS RTU , MODBUS ASCII , TAIE
RS232 , RS485 , TTL
Communication
Baud rate: 2400 , 4800 , 9600 , 19200 , 38400 bps.
Data bits : 8 , Stop bit : 1 or 2bit , Odd or Even parity.
Water/Dust proof
IP65
z
Special control output (OUT1)
Model
uTC52 uTC62 uTC72 uTC42 uTC92
1
φ
zero crossing
control(1
φ
SSR)
Available Not
available Available
Not
available
Available
3
φ
zero crossing
control(3
φ
SSR)
Not available
Available
Motor valve control
Available
1
φ
phase angle
control(1
φ
SCR)
Not available
Available
3
φ
phase angle
control(3
φ
SCR)
Not available
Available
z
Programmable RAMP/SOAK
Model
uPC52 uPC62 uPC72 uPC42 uPC92
Programmable
RAMP/SOAK
2 patterns with 8 segments each.
The 2 patterns can be linked together as 16 segments use.