TCL U-MATCH-R32 SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL
205
Height of the room
Select the applicable table
< 1.8m
Floor standing type
≥
1.8m
Wall mounted type
≥
2.2m
C
eiling type
3.Refer to the following table to check out the minimum construction area.
Ceiling type
Wall mounted type
Floor standing type
Weight (kg)
Area
(
m
2
)
Weight (kg)
Area
(
m
2
)
Weight (kg)
Area
(
m
2
)
< 1.224
—
< 1.224
—
< 1.224
—
1.224
0.956
1.224
1.43
1.224
12.9
1.4
1.25
1.4
1.87
1.4
16.8
1.6
1.63
1.6
2.44
1.6
22.0
1.8
2.07
1.8
3.09
1.8
27.8
2.0
2.55
2.0
3.81
2.0
34.3
2.2
3.09
2.2
4.61
2.2
41.5
2.4
3.68
2.4
5.49
2.4
49.4
2.6
4.31
2.6
6.44
2.6
58.0
2.8
5.00
2.8
7.47
2.8
67.3
3.0
5.74
3.0
8.58
3.0
77.2
3.2
6.54
3.2
9.76
3.2
87.9
3.4
7.38
3.4
11.0
3.4
99.2
3.6
8.27
3.6
12.4
3.6
111
3.8
9.22
3.8
13.8
3.8
124
4.0
10.2
4.0
15.3
4.0
137
4.2
11.3
4.2
16.8
4.2
151
4.4
12.4
4.4
18.5
4.4
166
4.6
13.5
4.6
20.2
4.6
182
4.8
14.7
4.8
22.0
4.8
198
5.0
16.0
5.0
23.8
5.0
215
5.2
17.3
5.2
25.8
5.2
232
5.4
18.6
5.4
27.8
5.4
250
5.6
20.0
5.6
29.9
5.6
269
5.8
21.5
5.8
32.1
5.8
289
6.0
23.0
6.0
34.3
6.0
309
6.2
24.5
6.2
36.6
6.2
330
6.4
26.1
6.4
39.1
6.4
351
6.6
27.8
6.6
41.5
6.6
374
6.8
29.5
6.8
44.1
6.8
397
7.0
31.3
7.0
46.7
7.0
420
7.2
33.1
7.2
49.4
7.2
445
7.4
34.9
7.4
52.2
7.4
470
7.6
36.9
7.6
55.1
7.6
496
7.8
38.8
7.8
58.0
7.8
522
8.0
40.8
8.0
61.0
8.0
549