TCL TCC-09C2HRH/DV Service Manual Download Page 17

TCL Air Conditioner Service Manual

 

 

17 

 

 

PART 

  Installation and Maintenance 

1. Notes for installation and maintenance 

Safety Precautions 
Important! 

Please read the safety of precautions carefully before installation and maintenance. The following contents 
are very important for installation and maintenance. Please follow the instructions bellow. 

● 

The installation or maintenance must accord with the instructions. 

● 

Comply with all national electrical codes and local electrical codes. 

● 

Pay attention to the warnings and cautions in this manual. 

● 

All installation and maintenance shall be performed by distributor or qualified person. 

● 

All electric work must be performed by licensed technician according to local regulations and instructions 
given in this manual. 

● 

Be  caution  during  installation  and  maintenance.  Prohibit  incorrect  operation  to  prevent  electric  shock, 
casualty and other accidents. 

 

Warnings

 

Electrical safety Precautions. 

 
1) 

Cut off the power supply of air conditioner before checking and maintenance. 

2) 

The air conditioner must apply specialized circuit and prohibit share the same circuit with other appliances. 

3) 

The air conditioner should be installed in suitable location and ensure the power plug is touchable. 

4) 

Make sure each wiring terminal is connected firmly during installation and maintenance. 

5) 

Have the unit adequately grounded. The grounding wire can’t be used for other purposes. 

6) 

Must apply protective accessories such as protective boards, cable-cross loop and wire clip. 

7) 

The live wire, neutral wire and grounding wire of power supply must be corresponding to the live wire, 
neutral wire and grounding wire of the air conditioner. 

8) 

The power cord and power connection wires can’t be pressed by hard objects. 

9) 

If power cord or connection wire is broken, it must be replaced by qualified person. 

10) 

If  the  power  cord  or  connection  wire  is  not  long  enough,  please  get  the  specialized  power  cord  or 
connection wire from the manufacture or distributor. Prohibit prolong the wire by yourself. 

11) 

For the air conditioner without plug, an air switch must be installed in the circuit. The air switch should be 
all-pole parting and the contact parting distance should be more then 3mm. 

12) 

Make sure all wires and pipes are connected properly and the valves are opened before energizing. 

13) 

Check if there is electric leakage on the unit body. If yes, please eliminate the electric leakage. 

14) 

Replace the fuse with a new one of the same specification if it is burnt down, don’t replace it with a cooper 
wire or conducting wire. 

15) 

If the unit is to be installed in a humid place, the circuit breaker must be installed. 

 

Installation Safety Precaution 

1) 

Select  the  installation  location  according  to  the  requirement  of  this  manual.  (See  the  requirements  in 
installation part). 

2) 

Handle unit transportation with care, the unit should not be carried by only one person if it is more than 
20kg. 

3) 

When installing the indoor unit and outdoor unit, a sufficient fixing bolt must be installed, make sure the 
installation supporter is firm. 

4) 

Ware safety belt if the height of working is above 2m. 

5) 

Use equipped components or appointed components during installation. 

6) 

Make sure no foreign objects are left in the unit after finishing installation. 

Summary of Contents for TCC-09C2HRH/DV

Page 1: ...TCL Air Conditioner Service Manual 1 Inverter air conditioner Service Manual Models TCC 09C2HRH DV TCC 12C2HRH DV TCC 18C2HRH DV...

Page 2: ...PART Installation and Maintenance 17 1 Notes for installation and maintenance 17 2 Installation 24 2 1 Location Selection 24 2 2 Indoor Unit Installation 25 2 3 Outdoor Unit Installation 29 2 4 Draina...

Page 3: ...responsible for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical mo...

Page 4: ...ir Conditioner Service Manual 4 Model Outdoor unit D E F G H I J K TCC 09C2HRH DV 712 498 234 415 291 225 48 5 52 TCC 12C2HRH DV 712 498 234 415 291 225 48 5 52 TCC 18C2HRH DV 780 605 290 516 349 314...

Page 5: ...e 3 way valve Compressor 4 way valve Muffler Muffler Heat exchange Condenser Heat exchange Evaporator Check valve Cooling Heating Capillary 24K Liquid side 2 way valve Gas side 3 way valve Compressor...

Page 6: ...B DISPLAY CN6 ROOM TEMPERATURE CN5 2 DC FAN MOTOR PCB SWING MOTOR 2 CN5 1 SWING MOTOR 1 OPTIONAL PART CN9 OPTIONAL PART PIPE TEMPERATURE 81102 015585 GND A B 12V G A B REMITE MONITOR CN12 POSITION SWI...

Page 7: ...TCL Air Conditioner Service Manual 7 MODEL TCC 18C2HRH DV PCB EEV...

Page 8: ...ng of horizontal flap up down or deactivate it CLEAN button ON OFF button TURBO button 9 SWING button To activate the swing of vertical flap left right or deactivate it 9 10 To active this function pr...

Page 9: ...r or or LOW FAN SPEED indicator 11 or or or or or MIDDLE FAN SPEED indicator 12 or or or or HIGH FAN SPEED indicator 13 or or or SLEEP indicator 14 COMFORTABLE SLEEP indicator optional 15 FEEL indicat...

Page 10: ...etween RT and ST shown as table Mode t RT ST COOLING t 1 FAN 1 t 1 HEATING t 1 5 2 2 Cooling mode 1 Temperature control 16 31 and the operation of fan speed and vane position according to preset 2 Com...

Page 11: ...l Frequency Decreasing NFD If 3 IPT 4 the frequency decreasing rate is 8Hz 90s until to the lower frequency limit 4 Fast Frequency Decreasing FFD If 2 IPT 3 the frequency decreasing rate is 16Hz 90s u...

Page 12: ...ture of OPT and OAT the max delay for the motor should be less than 160s 2 When switch on unit on heating mode ODU fan motor will delay 5s after compressor starts up 3 in the process of defrosting the...

Page 13: ...or operation within 2min if IPT 27 fan motor works in low speed 2 min then change to preset speed When RT 24 a Within 2 min after compressor start up working once IPT 27 fan motor will change to prese...

Page 14: ...cording to the SLEEP CURVE as designed Sleeping mode the unit can work 10 hours continuously after that it will quit from this mode and work as previous presetting 5 2 8 Emergency switch When the EMER...

Page 15: ...ately once the unit to be switched off on fan mode or changed to be heating mode from others Note If the defective failure can t be recovered the failure can t eliminate even if operation mode changed...

Page 16: ...eliminate immediately once the unit to be switched off or changed to fan mode Note If the defective failure can t be recovered the failure can t eliminate even if operation mode changed 5 2 11 Comple...

Page 17: ...e and grounding wire of power supply must be corresponding to the live wire neutral wire and grounding wire of the air conditioner 8 The power cord and power connection wires can t be pressed by hard...

Page 18: ...ssure rise and then compressor overheat or gas leak resulting in injury 5 When installing the unit make sure that connecting pipe is securely connected before the compressor starts running If compress...

Page 19: ...0 14 0 18 1 0 08 0 11 0 03 0 06 0 09 0 2 0 3 1 8 0 15 0 2 0 24 0 29 0 34 0 41 0 53 2 2 0 18 0 24 0 29 0 36 0 41 0 51 0 65 R32 0 306 0 6 0 68 0 9 1 08 1 32 1 53 1 87 2 41 1 1 14 1 51 1 8 2 2 2 54 3 12...

Page 20: ...lling an air conditioner of R32 R290 it is necessary to take appropriate anti static measures such as wear anti static clothing and gloves It is necessary to choose the location for installation or ma...

Page 21: ...itioner On the maintenance site there should be two or more kinds of dry powder carbon dioxide and foam fire extinguishers and that such fire extinguishers should be placed at stipulated positions wit...

Page 22: ...t is damaged to the extent that it is a must to open the refrigerating system for maintenance it is a must to carry the product back to the maintenance station for maintenance It is prohibited to weld...

Page 23: ...nfirm that the refrigerating system has been drained and the system has been cleaned and ensure that there has been no refrigerant in the outdoor unit It is necessary to close the stop valve of the ou...

Page 24: ...tion and inspection The place can ensure the indoor unit horizontally installed The place shall allow easy water drainage The place shall easily connect with the outdoor unit The place where air circu...

Page 25: ...TCL Air Conditioner Service Manual 25 More than 30cm More than 60cm More than 200cm More than 30cm More than 60cm Service space Fence or obstacles 2 2 Indoor Unit Installation...

Page 26: ...TCL Air Conditioner Service Manual 26...

Page 27: ...TCL Air Conditioner Service Manual 27...

Page 28: ...TCL Air Conditioner Service Manual 28...

Page 29: ...TCL Air Conditioner Service Manual 29...

Page 30: ...TCL Air Conditioner Service Manual 30...

Page 31: ...hold the inlet of the outdoor unit to prevent it from deforming Do not touch the fan with hands or other objects Do not lean it more than 45 and do not lay it sidelong Make concrete foundation accord...

Page 32: ...or unit Relationship between water flowrate and capacity of indoor unit Capacity x1000Btu Water flowrate l h 12 2 4 18 4 24 6 30 7 36 8 42 10 48 12 60 14 According to the above table to calculate the...

Page 33: ...vertical pipe is respectively 1m 1 5m and 1 5m 2 0m Each vertical pipe shall be equipped with not less than two hangers Overlarge hanger gap for horizontal pipe shall create bending thus leading to ai...

Page 34: ...n below 7 When unifying multiple drain pipes install the pipes as Figure 3 1 51 Select converging drain pipes whose gauge is suitable for the operating capacity of the unit take the cassette type unit...

Page 35: ...rtically and make sure it is not further than 300mm 11 3 4inch from the base of the drain outlet 4 Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting br...

Page 36: ...ome blocked and malfunction 2 5 Drainage Test 2 5 1 Water Leakage Test After finishing the construction of drainage pipe system fill the pipe with water and keep it for 24 hours to check whether there...

Page 37: ...Drain plug at the main water containing plate is used for eliminating accumulated water in water containing plate when maintaining air conditioner fault During normal operation the plug shall be fille...

Page 38: ...l trap should be installed every 6m 20ft of vertical suction line riser 2 6 3 The Procedure of Connecting Pipes 2 6 3 1 Choose the Pipe Size according to the Specification Table 2 6 3 2 Confirm the Cr...

Page 39: ...ipes more than three times 4 When bending the pipe do not bend it as is The pipe will be collapsed In this case cut the heat insulating pipe with a sharp cutter as shown in Figure 3 3 3 and bend it af...

Page 40: ...ng table for different pipe connection Pipe Diameter Torque Sketch map kgf cm N cm 1 4 6 35 144 176 1420 1720 3 8 9 52 333 407 3270 3990 1 2 12 7 504 616 4950 6030 5 8 15 9 630 770 6180 7540 3 4 19 99...

Page 41: ...nifold pressure gauge to vacuum pump 3 Open the Low Pressure side of the manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to empty the gas in the system 5 Run the vacuum pum...

Page 42: ...liquid state Before recharging The air in the flexible pipe and manifold gauge should be exhausted After finished refrigerant recharge process check whether there is refrigerant leakage at the connect...

Page 43: ...temperature of condensate drainage water is very low If insulation is not enough it shall form dew and cause leakage to damage the house decoration 2 9 2 3 Insulation Material Selection for Drainage...

Page 44: ...nd Display board IDU failure Display board and main PCB EE ODU EEPROM failure 1 ODU PCB broken 2 Try to re power on AC unit EF ODU DC fan motor failure Fan motor ODU PCB EU ODU Voltage test circuit ab...

Page 45: ...e current protection phase current of compressor Querying by press remote controller FF Limiting Reducing frequency for Module temperature protection Querying by press remote controller FH Limiting Re...

Page 46: ...eplace re connect Check and re connect No n Check voltage from IDU terminal btw L N is there 220V Replace IDU PCB No Yes Yes Is the ODU PCB LED5 ON Replace ODU PCB Check voltage from IDU terminal btw...

Page 47: ...r and or coil temperature sensor failure Start Display E1or E2 Re connect Is the sensor well connected to PCB Multi meter check the sensor is it open or short circuit Replace the sensor No Yes Yes Rep...

Page 48: ...nnect Multi meter check resistance of fan motor is there open or short circuit of winding Replace IDU PCB Replace fan motor Yes Yes No No End Turn the fan blades by hand while power off condition Can...

Page 49: ...t unit will display failure code as E3 E7 or E8 IDU and ODU turns off When the sensor resistance recovery unit revert to be standby customer can switch on the unit directly Start Display E3 E7 or E8 R...

Page 50: ...unit can t be recovered to operation except press ON OFF button Display E9 Re power on unit running for 30 min and check the failure code display Normal protection Display F9 or FA first then E9 Repl...

Page 51: ...tor well connect to PCB Re connect 1 For built in control 5pins motor check the Vm 310V Vcc 15V 2 For external control 3pins motor test voltage btw U V W normally from DC 20 200V Replace ODU PCB Check...

Page 52: ...r failure After power relay works when tested voltage effective value less than 50V for 3s continuously unit will display EU Start Display EU Test voltage btw ODU terminal L N more than 50V End Replac...

Page 53: ...o slowly Replace ODU fan motor Yes Replace compressor End Yes No Yes P0 disappear test voltage btw U V W normally from DC 20 200V Unit works normal Turn unit on to check whether the malfunction is eli...

Page 54: ...Test voltage on the big size electrolytic capacitor of ODU PCB When DC busbar voltage V DC420V or V DC150V unit will recover back to previous status while DC190V V DC410V Display P1 Is the power suppl...

Page 55: ...han Imax it will stop and display P2 protection Note for different AC model Imax has difference valve Display P2 ODU fan motor works Replace fan motor IDU filter or ODU condenser too dirty Clean IDU f...

Page 56: ...ondenser too dirty or filter blocked IDU ODU fan motor running slowly or stopped Capillary blocked Is the unit gas pressure normal cooling0 8 1 3Mpa heating2 0 3 6Mpa Replace ODU PCB Clean IDU filter...

Page 57: ...P5 Switch on unit after minutes Display P5 Normal protection No Yes IDU filter dirty Yes Clean filter IDU air inlet blocked No Clean Yes Can fan blade rotate freely Check and repair fan blade Fan moto...

Page 58: ...e OPT 62 MCU will switch off outdoor unit and show P6 failure code Display P6 ODU fan motor works normal Replace OPT sensor Replace ODU PCB Fan motor broken Replace fan motor End No No Yes Yes P6 disa...

Page 59: ...62 ODU PCB will switch off outdoor unit and show P7 failure code Display P7 ODU fan motor works normal Replace IPT sensor Replace IDU PCB Fan motor broken Replace fan motor End No No Yes Yes P7 disap...

Page 60: ...elay the IDU will show P8 failure code 1 On Cooling or Dry mode ODU ambient temperature OAT 20 or OAT 63 2 On Heating mode a OAT 40 or b 30 OAT 40 and RT 35 Display P8 Ambient temperature under spec r...

Page 61: ...ion of IDU coil temperature If there is mistake installer forgetting to open the 2 way or 3 way valve on ODU the gas can t flow in the cooling system it will show F4 protection Start Display F4 Open t...

Page 62: ...f compressor current it will show F6 protection Display F6 Check compressor wiring connector is it well connected Re connect The Compressor wiring in good quality Replace the wires Compressor phase cu...

Page 63: ...and heat sink Fix the screw ODU cooling system abnormal Compressor with big running current 9 12K 6 7A 18 24K 7 9A Low pressure normal 0 8 1 2Mpa IPM temperature circuit abnormal Replace ODU PCB Is th...

Page 64: ...5 or even more after compressor works for 8min unit will show F8 code Display F8 Is there 220V voltage on the 4 way valve Replace ODU PCB Multimeter test the valve coil resistance does it open or sho...

Page 65: ...ll show Fy failure code Check the pipe connection any gas leakage Repair and charge new gas as SPEC Check the room evaporator coil temperature No Is the temperature difference more than 2 btw RT IPT a...

Page 66: ...00276 Cover of motor 1 10 25001 000049 Fan Motor 1 11 45014 002903 Cotton Base assembly 1 12 A5006 000008 Base Rear Foam Assembly 1 13 45013 000054 Left trim strip 1 14 45001 000002 Installation Plate...

Page 67: ...31 45005 000331 Air Guide Splash motor cover 1 32 35010 000002 Display panel 1 33 41505 000323 Display Film 1 34 35006 000001 Buckle base 2 35 46701 000003 Buckle cover 2 36 45014 002709 Air filter 1...

Page 68: ...08 000209 4 way valve 1 12 92007 005836 4 way valve assembly 1 13 41202 000177 Base 1 14 41205 000211 Right plate 1 15 92008 000051 Two way valve 1 16 41204 000051 Valve supporter 1 17 92008 000146 Th...

Page 69: ...4 000542 Compressor and accessories 1 11 92008 000209 4 way valve 1 12 92007 005836 4 way valve assembly 1 13 41202 000177 Base 1 14 41205 000211 Right plate 1 15 92008 000051 Two way valve 1 16 41204...

Page 70: ...ries 1 11 92008 000207 4 way valve 1 12 92007 000445 4 way valve assembly 1 13 41202 000156 Base 1 14 41205 000082 Right plate 1 15 92008 000051 Two way valve 1 16 41204 000041 Valve supporter 1 17 92...

Page 71: ...ing work in the following procedure A Cut the pipes and the cable 1 Use the piping kit accessory or the pipes purchased locally 2 Measure the distance between the indoor and the outdoor unit 3 Cut the...

Page 72: ...627 4 477 22 5 621 2 621 67 1 175 0 936 22 41 403 4 452 23 5 404 2 572 68 1 139 0 913 21 39 305 4 426 24 5 198 2 524 69 1 105 0 890 20 37 326 4 399 25 5 000 2 475 70 1 072 0 868 19 35 458 4 371 26 4...

Page 73: ...nit sensor temperature characteristics TEMP R min k Ohm R t k Ohm R max k Ohm TEMP R min k Ohm R t k Ohm R max k Ohm TEMP R min k Ohm R t k Ohm R max k Ohm 30 283 3 322 9 367 7 24 19 36 20 89 22 52 78...

Page 74: ...9997 1 045 3 50 03 55 05 60 52 57 5 255 5 522 5 798 111 0 9283 0 9719 1 016 4 47 71 52 44 57 59 58 5 07 5 323 5 585 112 0 9021 0 9451 0 9892 5 45 5 49 97 54 82 59 4 891 5 132 5 381 113 0 8765 0 9191...

Page 75: ...TCL Air Conditioner Service Manual 75 R Resistance Resistance at 25 20 k TH3 Outdoor unit discharge pipe sensor Before measuring resistance disconnect connectors as shown above...