7

(5) Defrost 

Defrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the defrost 
sensor. 

 

 Defrost starting conditions 

When the conditions of a) or b) is satisfy, the defrosting operation starts. 
a) Under the heating operation, the compressor cumulative operation time exceeds 

4

0 minutes and the 

temperature of the outdoor defrost sensor reads lower than 

6

 continuously for 3minutes. 

 

b) Under the heating operation, the compressor cumulative operation time exceeds 

4

0 minutes, if the 

indoor pipe temperature 

is

 lower than 

32

 continuously for 

3

minutes. 

Note: If haven’t the outdoor pipe temperature sensor that use the condition b) to defrost, against 
use the condition a). 

 

 Defrost terminating conditions 

When the condition c) or d) is satisfy, the defrosting operation stops. 
c) The outdoor 

pipe temperature is higher than

 

20

d) The defrosting time exceeds 10 minutes. 

 

 Defrosting time chart 

 

 

     Outdoor Fan       ON                  OFF                ON 
 
 
          Rever

s

ing   Valve            ON                                    OFF                                      ON  

 
 
 

 
Compressor   Relay      ON          OFF                            ON                              OFF            ON  
 
                        39S   5S  Defrost Count MAX 12min  19S   15S          t 
 

(6) Assistant Thermistor Function 

Assistant thermistor is add the thermitor of the electricity to rise the heating capacity automatically not 
effected by the signal of the remote controller about assistant thermistor ON/OFF buttons. 

1) When the condition all of A~G are satisfy, the assistant thermistor 

should be on

A. Under the heating operation, the compressor 

has been running

 over than 

2

 minutes. 

B. The indoor fan operates in normal. 
C. The system operates not in defrosting. 
D. The assistant thermistor 

has been

 off over than 

1

0 seconds. 

E. The set

ted

 temperature is 3

 

higher

 than the room temperature

 and 15ºC<T1<25ºC.

F. The room temperature 

is lower

 than 

15

G. 

The indoor pipe temperature 

is lower than

 4

5

 . 

2) When one of the conditions of A~E is satisfy, the assistant thermistor is off. 

A. The compressor is  off. 
B. 

The room temperature 

higher than

 2

5

 . 

C. 

The indoor pipe temperature 

is higher than

 

50

D. 

The indoor fan is stopped. 

6.  “FAN” mode operation   

Summary of Contents for TAC-42CF

Page 1: ...ING AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 5 5 EXPLOSION VIEW 12 6 PARTS LIST 18 Models TAC 42CF TAC 42CHF TCL SERVICE MANUAL No TE040720 ...

Page 2: ...nformation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior notice The accurate specifications are presented on the nameplate label How to order spare parts To have your order filled promptly and correctly please furnish the following information 1 Model No wi...

Page 3: ...e φ9 53 Expansion device Capillary tube Defrosting system Microcomputer controlled reverse system Fan System Indoor air circulation m3 h 1000 1000 Indoor fan type Cross flow Cross flow Cooling rpm 550 480 380 550 480 380 Heating rpm N A 550 480 380 Dry rpm 380 380 Indoor fan speed H M L Sleep rpm 380 380 Indoor fan motor output W 160 160 Outdoor air circulation m 3 h Outdoor fan type Propeller fan...

Page 4: ...TION MODE Selection Button Used to select the type of operation mode AUTO Cooling Dry Fan Only for Cooling Only and Heating Only for Heat Pump FAN SPEED CONTROL Button Used to select the indoor fan motor speed Auto High Mid and Low TCL Air Conditioner Service Manual 4 TCL Air Conditioner Service Manual ...

Page 5: ...temperature and time ON TIMER Button Used to select ON TIMER operation OFF TIMER Button Used to select OFF TIMER operation The indication symbols on LCD A U T O Indicator Sleep Mode Indicator Clock Indicator Cooling Indicator Air Flow Direction Indicator ON TIMER Indicator Dry Indicator Set Room Temp Indicator OFF TIMER Indicator Fan Indicator Fan Speed Indicator Order of ON and OFF Timer Heating ...

Page 6: ... Control During HEATING operation the outdoor fan motor and compressor are controlled by the indoor pipe temperature to prevent the high temperature of compressor Outdoor fan OFF 56 Outdoor fan ON 50 Compressor OFF 60 Compressor ON 50 2 AUTO Mode Operation 1 When the AUTO mode is selected the operation mode and initial set temperature are determined by the initial room temperature at start up of t...

Page 7: ... be controlled 5 HEATING Mode Operation Only available for Heat Pump 1 When the HEATING mode is selected without setting temperature the system will set the temperature at 23 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the setting by the remote controller and the operation is as following Set Temp 1 Set Temp 1 Room Temp Tim...

Page 8: ...xceeds 10 minutes Defrosting time chart Outdoor Fan ON OFF ON Reversing Valve ON OFF ON Compressor Relay ON OFF ON OFF ON 39S 5S Defrost Count MAX 12min 19S 15S t 6 Assistant Thermistor Function Assistant thermistor is add the thermitor of the electricity to rise the heating capacity automatically not effected by the signal of the remote controller about assistant thermistor ON OFF buttons 1 When ...

Page 9: ...rocessor to feedback the rotational frequency Comparing the current rotational frequency with the target rotational frequency the microprocessor adjusts fan motor electric to make the current rotational frequency close to the target rotational frequency With this control when the fan speed is switched the rotational frequency changes smoothly 2 When the rotational frequency feedback signal has not...

Page 10: ...matic mode only possible when the feel Cool or Heat mode is selected by pressing the Fan button The ventilator always operates in the Auto mode when the Dry mode is selected Select Swing or no Swing by pressing the Swing button Press the Timer button h flashes Use the button to select the time at which the air conditioner must activate between 0 and 10 hours can be set at every half hour between 1...

Page 11: ... during normal operation 14 AUTO RESTART Function Option When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor electric control PCB The AUTO RESTART function sets to work the moment power has restored after power failure Then the unit will restart automatically 15 Failure Display and Handling a The failure of ...

Page 12: ...r stops the indoor fan operates in cold air prevention control The system doesn t receive the signal of remoter controller except the signal of shut off it When the system check the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the compressor is stopped the outdoor fan and indoor fan is stopped and display the failure The system ...

Page 13: ...TCL Air Conditioner Service Manual 12 WIRING DISGRAM MODEL TAC 42CHF INDOOR UNIT OUTDOOR UNIT ...

Page 14: ...TCL Air Conditioner Service Manual 13 MODEL TAC 42CF INDOOR UNIT OUTDOOR UINT ...

Page 15: ...or COOLING HEATING 214590114 FRONT PLATE 1084590106 FAN GUARD 1100070001 COMPRESSOR 1120160003 LIQUID STORE CAN 1120120010 TWO WAY VALVE 1124590113 CAPILLARY ASSEMBLY same for heating cooling AND cooling only 1094590101 OUTDOOR PCB for heating cooling 1094590201 OUTDOOR PCB for only cooling 1214590105 PARTITION 1120130012 THREE WAY VALVE 1214590101 BASE 1214590103 RIGHT PLATE 1214590110 TOP COVER ...

Page 16: ...090210 OPERATION PANEL 1094090202 OPERATION PCB for heating cooling 1094090404 OPERATION PCB for only cooling 1074090121 INDOOR GRILLE 1074090122 AIR FILLTER 1074090121 GRILLE 1214090116 MIDLLE PANEL 1170010004 SWING MOTOR 1074090108 HORIZONTAL VANE 1074090110 VERTICAL VANE 1074090103 BASE ...

Page 17: ...TCL AIR CON SERVICE MANUL 1214090121 EVAPORATOR ASSEMBLY 1094090301 MAIN PCB for heating cooling 1094091102 MAIN PCB for only cooling 1170030010 INDOOR MOTOR 1070010004 INDOOR FAN ...

Reviews: