TCL TAC-09CHSA/GI Service Manual Download Page 9

TCL Air Conditioner Service Manual 

some reason, when power supply come back again, the AUTO-RESTART function will set 
synchronously and automatically to work. So the air conditioner would work at the same mode 
before.  

Auto-restart Pre-setting (optional)

If Auto-restart function is needed, follow the steps below to activate this function: 
1) Pulling the air-con's plug out of socket. 
2) Pressing and holding the Emergency button (ON/OFF) on the indoor, then insert the plug 
into the socket again. 
3) Keep pressing the Emergency button for more than 10 seconds until three short beeps are 
heard. The 

Auto-restart 

function has been started. 

9.  Protection and Failure Display 

 

z

  When protection display is available, controller will show error code, digital LED shows 

error code and setting temperature by turns.     

z

  If there is more than one failure, it will show at first that in front of the error list. 

z

  Protection display function can be selected in hardware, and the default don’t display; 

z

  To insure of in and out communist is credibility, the failures relate to outdoor unit will 

remain failure state for 2 minutes max after recovered. 

z

  In all failures, only sensor failures don’t have to repower to cancel. 

z

 

Error list 

Failure type 

LED CODE 

DIGITAL LED CODE 

 

In and out communication failure 

RUN

TIMER –both winking  

E0 

Outdoor communication failure 

RUN

TIMER –both winking 

EC 

Outdoor sensor 

RUN-1 time/8s 

E1 

Indoor coil temperature sensor 

RUN-2 times /8s 

E2 

Outdoor coil temperature sensor 

RUN-3 times /8s 

E3 

System abnormity 

RUN-4 times /8s 

E4 

Type mismatch   

RUN-5 times /8s 

E5 

Indoor fan motor 

RUN-6 times /8s 

E6 

Outdoor temperature sensor 

RUN-7 times /8s 

E7 

Discharge temperature sensor 

RUN-8 times /8s 

E8 

Invert module abnormity 

RUN-9 times /8s 

E9 

Outdoor fan motor

DC

 RUN-10 

times 

/8s 

EF 

Current sensor 

RUN

11 times /8s 

EA 

EEPROM failure 

RUN-12 times /8s 

EE 

Top of    compressor temperature switch

RUN-13 times /8s 

EP 

Voltage sensor 

RUN-14 times /8s 

EU 

 

 

 

 

 

 

 

 

                                                                                           

 

9

 

Summary of Contents for TAC-09CHSA/GI

Page 1: ...PE AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 11 5 EXPLOSION VIEW 12 6 PARTS LIST 13 Models TAC 09CHSA GI TAC 12CHSA GI TCL SERVI...

Page 2: ...formation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior n...

Page 3: ...H x D Outdoor mm 760 560 260 760 560 260 Indoor kg 8 5 8 5 Outdoor kg 30 34 Packing dimensions Indoor mm 883 325 271 883 325 273 W x H x D Outdoor mm 863 598 381 863 598 383 Indoor kg 10 5 10 5 Outdoo...

Page 4: ...ler 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Page 5: ...is overload controller shut down the unit immediately and show error code 6 Compressor abnormity protection When compressor start on or in the process of running if there is no feedback to controller...

Page 6: ...or will run automatically 3 Auto fan control in cooling mode In cooling mode include cooling in I feel mode fan speed is determined by t as the following diagram 1 5 1 0 3 0 3 5 t come down high fan t...

Page 7: ...ocess of defrosting 4 Defrosting Defrosting is controlled by the microprocessor When one of the following conditions is satisfied unit will come into defrosting a Outdoor heat exchanger Temperature OP...

Page 8: ...later z When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 2hour later z After the System operates in SLEEP mode for 8 hours it will stop auto...

Page 9: ...of the error list z Protection display function can be selected in hardware and the default don t display z To insure of in and out communist is credibility the failures relate to outdoor unit will r...

Page 10: ...tdoor power board when compressor is running it is normally light when no feedback of signal to power board from compressor it will wink by lighting 1s and going out 1s If failures happened it will li...

Page 11: ...TCL Air Conditioner Service Manual Wiring diagram Model TAC 09CHSA GI TAC 12CHSA GI Indoor unit Outdoor Unit 11...

Page 12: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Indoor unit Model TAC 09CHSA GI TAC 12CHSA GI 12...

Page 13: ...filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal 1...

Page 14: ...r filter 2 13 1070321113 panel 1 14 1070321107 Ornament strip 1 15 1170120045 Power supply cord 1 16 1070320104 vane 1 17 1070110008 Drainage hose 1 18 1070040004 Cable clamp 1 19 1170200042 Terminal...

Page 15: ...TCL Air Conditioner Service Manual EXPLOSION VIEW Outdoor unit Model TAC 09CHSA GI TAC 12CHSA GI 15...

Page 16: ...necting pipe 1 15 1120250425 Suction pipe 1 16 1120250426 Discharge pipe 1 17 1120250428 Condenser connecting pipe 1 18 1120250615 Capillary assembly 1 19 1140020011 Sound arrester 1 750 350 8 20 1080...

Page 17: ...nual 17 PART LIST Outdoor unit Model TAC 09CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Page 18: ...pipe 1 15 1120321529 Suction pipe 1 16 1120321530 Discharge pipe 1 17 1120321532 Condenser connecting pipe 1 18 1120321525 Capillary assembly 1 19 1140020011 Sound arrester 750 350 8 1 20 1080050002 R...

Page 19: ...nual 19 PART LIST Outdoor unit Model TAC 12CHSA GI No Part No Part Name Q ty Remark 38 1190070020 Base carton 1 39 1190700302 Cabinet carton 1 40 1190070022 Base foaming 1 41 1190070021 Cover foaming...

Reviews: