HGP Kit Manual
5.0 PQconnect
42
Write Parameters:
Table 20: Network Interface INPUT/Setpoint Register Map
Parameter Name
I/O Reg
Address
Offset
Signal
Direction
to Filter
Data Values and Examples
Description
SYS_PF_STEP_1_KVAR
576
Input
DEFAULT:
5 = 5 kVAR Steps
Range: 1 to 200 kVAR
Desired filter kVAR for contactor to
enable*
SYS_PF_STEP_2_KVAR
577
Input
DEFAULT:
5 = 5 kVAR Steps
Range: 1 to 200 kVAR
Filter Second Tuned Circuit kVAR
(Only used for filters with dual tuned
circuits) *
CNT_AUTO_RECLOSE_DELAY
580
Input
DEFAULT:
10 = 10 seconds
Range: 10 to 3600 seconds
Contactor auto re-close delay time*
CNT_POWER_ON_DELAY
581
Input
DEFAULT:
1 = 1 second
Range: 0 to 3600 seconds
System Power on Delay*
CNT_AUTO_RECLOSE_ATTEMPTS
582
Input
DEFAULT:
5 = 5 attempts
Range: 1 to 15
Maximum number of contactors auto
re-close attempts allowed*
CNT_AUTO_RECLOSE_TIMESPAN
583
Input
DEFAULT:
600 = 600 seconds
Range: 300 to 3600 seconds
Maximum number of contactors auto
re-close attempts time span*
MB_SLAVE_ADDRESS
600
Input
DEFAULT:
= 10
Range: 0 to 255
Modbus RTU Device Slave Address*
MB_BAUD_RATE
601
Input
DEFAULT:
11520 = 115200
baud rate
3840 = 38400 baud rate
960 = 9600 baud rate
Modbus RTU Device Baud Rate*
MB_PARITY
602
Input
0 = None
1 = Odd
DEFAULT:
2 = Even
Modbus RTU Device Parity*
SYS_INPUT_1_CONFIG
610
Input
DEFAULT:
0 = Disabled
1 = Tuning Reactor Thermal
Switch Input
2 = Line Reactor Thermal
Switch Input
3 = Reset Command
4 = External Control Input
Customer external control input*
SYS_INPUT_2_CONFIG
611
Input
DEFAULT:
0 = Disabled
1 = Tuning Reactor Thermal
Switch Input
2 = Line Reactor Thermal
Switch Input
3 = Reset Command
4 = External Control Input
Customer external control inputs*
PHASE_ROTATION
693
Input
DEFAULT:
1 = ABC Rotation
Expected
2 = ACB Rotation Expected
Filter expected input phase
orientation*
SYS_MAG_CAL_ENABLE
700
Input
0 = Disable
1 = Enable
System magnitude Calibration
SYS_I_LINE_CAL_A
710
Input
1000 = 100A
Range: 3 to 1500
Input current measured on A phase of
the filter*
Note: For calibration setup