6.3.3.   Steam exchanger 

With  regard  to  general  maintenance  operations,  follow 
the steps described in 6.3.1. 
In  order  to  perform  maintenance  work  on  an  Air 
Treatment  Unit  with  steam  heat  exchanger  in  absolute 
safety,  you  must  make  provision  for  the  automatic  shut-
off of the steam supply in the case of motor fan unit stop. 

6.3.4.   Direct expansion exchanger 

With  regard  to  general  maintenance  operations,  follow 
the steps described in 6.3.1. 
TCF  recommends  you  check,  on  at  least  a  weekly  basis, 
that there are no gas leaks from the distribution heads. In 
the  event  of  gas  leaks,  the  COOLING  CHARGE  would  be 
lost and the whole system compromised. 

6.4. 

HUMIDIFIER SECTIONS 

An  efficient  humidification  system  has  a  limited  life  that 
depends on various factors, including: 
-  the  type  of  operation  (expendable,  with  circulation,  cell 
block, spray nozzles, steam, compressed air) 
- the total hardness of the feed water (section 4.3.1) 
-  the  dust  concentration  in  the  treated  ain  i.e.  the  Unit's 
filtration efficiency. 

6.4.1.   Humidification with spray nozzles 

It  is  advisable  to  CHECK  EVERYWEEK  THAT  THE  SPRAY 
NOZZLES FORM A REGULAR GONE-SHAPED JET. 
In the case of scale you must: 
- remove the malfunctioning nozzles from the distribution 
ramp 
-  clean  the  nozzles  on  if  they  are  damaged,  replace  them 
with others that have the same characteristics 
-  restore  proper  working  conditions  prior  to  restarting 
the humidification system. 

6.4.2.   Humidification with cell block 

BEFORE  EACH  WORKING  SEASON,  in  order  to  avoid 
interruptions,  you  must  visually  check  that  the  cell  block 
is  evenly  wetted;  if  you  observe  water  jets  on  its  surface 
you  must  restore  an  even  water  flow  by  adjusting  the 
valve. 
THE CELL BLOCK CANNOT BE RECONDITIONED. 
When it is fouled you must replace it as follows: 
- stop the electrical pump 
- cut off the water feed using the relevant gate 
-  let  the  block  dry  completely,  keeping  the  fan  in 
operation 
-  remove  the  frame  housing  the  block  by  undoing  the 
securing  screws  and  lift  it  out  of  the  unit  through  the 
inspection door 
- extract the fouled block from the housing and replace it 
with  another  of  the  same  size.  Take  care  with  the 
direction  of  fluid  flow:  the  water  which  runs  along  the 
veins  of  the  block  must  intersect  the  air  flow  in  reverse 
current (fig. 36) 

-  Check  the  condition  of  the  distributor  tube  and,  if 
necessary, replace it 
-    Restore  proper  operating  conditions  before  restarting 
the humidification system. 

6.4.3.   Humidification with circulating pump 

- AT THE START OF EACH WORKING SEASON, in order to 
keep the humidification system in efficient condition, you 
must check that the pump is working properly. lf it is not, 
remove  and  clean  it.  If  the  pump  still  does  not  work 
properly after cleaning, you must replace it. 
-  Make  sure  that  the  water  level  inside  the  tank  is  20-30 
mm below the overflow to  avoid flooding and  ensure the 
pump has a sufficient water head. If the pump sucks in air, 
it  will  overheat  and  sustain  irreparable  damage.  If 
necessary,  adjust  the  float  to  maintain  the  correct  water 
level 
-  To  prevent  flooding  of  the  machine  and  the  installation 
room,  remove  any  scale  and  sludge  that  might  obstruct 
the drain every month. 

6.4.4.   Ultrasonic, 

steam 

(submerged 

electrodes), 

compressed air humidifiers . 

For  Air  Treatment  Units  with  these  types  of 
humidification  system,  consult  the  TECHNICAL  MANUAL 
supplied with the humidifier 

6.4.5.   Steam  humidification  with  submerged  heating 

elements 

In  order  to  preserve  the  heating  elements,  maintain  the 
efficiency of the humidification system and prevent over-
flows  and  flooding  of  the  installation  site,  you  must 
perform the following steps at least once a month: 
- check that the microswitch is working properly 
- remove any deposits from the elements and the tank. 

Summary of Contents for ZAE Series

Page 1: ...1 INSTALLATION OPERATION AND MAINTENANCE MANUAL AIR HANDLING UNITS ZAE SERIES ...

Page 2: ...ging duct section between Unit delivery inlet and obstruction 18 5 3 2 Elbows 19 5 3 3 Control air locks 19 6 MAINTENANCE 20 6 1 FOREWORD 20 6 2 FILTRATION SECTIONS 20 6 2 1 Reconditionable synthetic filters 20 6 2 2 Metal filters 20 6 2 3 Rotary filters 21 6 2 4 Reconditionable bag filters 21 6 2 5 Non reconditionable medium high efficiency filtration sections 21 6 2 5 1 Non reconditionable bag f...

Page 3: ... ryto commissioning The recommendations that follow are intended to ensure continuous operation of the Air Treatment Unit and long machine life The procedures described below should be followed by skilled personnel with a good working knowledge of air conditioning systems engineering and air treatment units even though the unit can be operated by those unfamiliar with air treatment thanks to the m...

Page 4: ...g product compliance with prevailing European Union machine directives 2 2 PACKING The Air Treatment Units are usually supplied as fully assembled monoblocks Only if the customer expressly requests it can the units be broken down into several sections to facilitate transportation and carriage through narrow apertures stairs or corridors Transportation of the machines both monoblock and broken down...

Page 5: ...steps must be taken first Prior to installation position the Unit and the accessories in a place affording the best possible protection against accidental knocks dust and atmospheric agents Carefully cover the inlets and outlets to prevent foreign matter from entering the unit and damaging the internal components Extract the pre filters from the Unit and put them in a protected place to preserve t...

Page 6: ...nctioning of the condensate drains difficulty in opening and closing the inspection doors The horizontal alignment of the support surface must be checked with a SPIRIT LEVEL adjustments may be made using STEEL SHIMS 3 3 3 Vibration damping In order to ensure effective protection against vibrations the Air Treatment Unit must be installed as follows suitable DAMPERS in material designed to withstan...

Page 7: ... assembled parts are perfectly aligned and level fig 8 Fasten the sections together with screws in the holes provided The holes are located on the inside of the corners and in the case of dimensions greater than 1 3 m also in a midway position The screw fastening areas can usually be accessed from the inspection doors Otherwise you must remove the panels next to the area involved Should the Unit b...

Page 8: ...pport the connecting pipes The weight of the pipes must under no circumstances bear down on the manifold 4 2 1 Water exchange In order to ensure an optimum heat exchange you must WASH the heat exchanger before connecting it to the water mains once installed in a workmanlike fashion any air present in the hydraulic circuit must be expelled using the relevant valve To allow easy extraction of the ex...

Page 9: ...ons to prevent the likelihood of rupture at the joint between manifolds and copper pipes In order to ensure correct operation of the thermal expansion valve the bulb of the valve must be in perfect contact with the intake line and fitted on the outside of the air flow so as not to be affected by it Special care must be taken with the SIPHONING of these exchangers to ensure the maximum heat exchang...

Page 10: ...be taken to ensure that the base is level see section 3 3 2 The steam system must be complete with all the necessary regulating filtration and safety devices which must be correctly sized Each heat exchanger must be fitted with a condensate drain which must be oversized to allow drainage of the greater quantity of condensate that is formed during system start up Provision must also be made for the...

Page 11: ...arise in which there is no water in the tank the pump motor would overheat and be irreparably damaged Conversely if there is too much water in the tank an overflow may result leading to flooding of the unit and the installation room 4 3 5 Ultrasonic steam submerged electrodes compressed air humidification For Air Treatment Units with the above listed types of humidification you should consult the ...

Page 12: ...tion of the prefilters located in the relevant counter frames with safety springs or guides The electrical connection and installation instructions for the rotary filtration section are provided in the specific manual provided The instructions for introduction of the reconditionable filtration diaphragm are set out in the maintenance chapter 6 2 3 After removing the filters from the packing in whi...

Page 13: ... motor start up system is obtained by connecting the motor direct to the power supply However this method has limitations due to the high start up current pick UD this type of start up is recommended for power ratings of up to 5 5 KW at which TCF installs 4 pole 220 380 V three phase motors as standard The wiring diagrams are shown in fig 27 4 6 1 2 Connecting with delta star starter If the motor ...

Page 14: ...f the same size but with separate windings 4 6 1 4 Permitted start time With regard to the temperature increase the start up time of a motor may not exceed the value shown in table 1 In the case of repeated starts with unchanging rated power the temperature of the motor must be the same as it was before the first start Therefore in order for the values in the table to be valid it is assumed that t...

Page 15: ...cularly important both during the design and installation phases The sound pressure values of our machines are indicated In our technical catalogues or can be supplied directly by our Technical Department according to the requested air moving characteristics Being therefore aware of the sound emissions produced by the Unit the Designer must make sure that in treated environments maximum values lai...

Page 16: ... check that the motor protection devices are sized for the maximum amperage corresponding to the rated value lf the protection devices are sized for an amperage in excess of the rated value you must make sure that the working range is sufficient 5 2 2 Flowrate check Using an oil or water column pressure gauge or an analogue and or digital gauge check the FLOW RESISTANCE in the various filtration s...

Page 17: ...er operating conditions should be made on the remote control power switches inside the control board using an amperometer clamp Under no circumstances must the measurements be made directly on the motor terminals since this is possible only with the inspection door open a condition that would alter the length of the air circuit and therefore the working point of the fans Descend vertically from th...

Page 18: ...M based on the charts developed by AMCA AIR MOVING AND CONDITIONING ASSOCIATION To calculate the additional flow resistance a graph is used which presents a family of straight lines on logarithmic velocity flow resistance coordinates Each line which is identified by a different letter of the alphabet represents an abnormal situation that determines an additional flow resistance AMCA lists the adve...

Page 19: ...FLOW RESISTANCE VALUES according to the Se sp ratio should the locks be installed on the delivery inlet If the air locks are supplied by TCE consult the SAL air lock technical bulletin Abnormal situations in relation to the reference standard may also occur on the intake and are basically connected with the possible formation of eddies caused by curves in the inlet conduit in conflict with the fan...

Page 20: ...the filtration diaphragm is washed without removing it from the frame if necessary using domestic detergents To avoid damaging the filter the temperature of the water must not exceed 50 C Do not use solvents or caustic soda Let the diaphragm dry by evaporation and refit it only when it is perfectly dry TCF advises you to CHECK THE CONDITION OF THE FILTERS ON A WEEKLY BASIS THE PREFILTERS MUST BE R...

Page 21: ...he aperture uppermost rinse them with a weak jet of warm water 50 C max letting the impurities run out at the bottom through the filtration diaphragm let the filters dry thoroughly by evaporation before refitting them Do not use air jets to dry them In this way the filters can be cleaned 2 3 times after which the filter s characteristics will be compromised and it will have to be replaced 6 2 5 No...

Page 22: ...freezing with the arrival of winter For this purpose TCF recommends the following steps In the case of prolonged idleness of the heat exchanger circuits they should be completed drained Where an anti freeze system based on heating elements is provided to protect the exchanger make sure that the control board is constantly powered up On systems operating with anti freeze check its efficiency and to...

Page 23: ...ows stop the electrical pump cut off the water feed using the relevant gate let the block dry completely keeping the fan in operation remove the frame housing the block by undoing the securing screws and lift it out of the unit through the inspection door extract the fouled block from the housing and replace it with another of the same size Take care with the direction of fluid flow the water whic...

Page 24: ...ed with grease nipples require periodic lubrication The greasing intervals under normal operating conditions are shown in Table 11 TABLE 10 Greasing of motor bearing NOTE The bearings must be greased more frequently in harsh operating conditions 6 5 3 Drive In order to ensure optimum drive efficiency and to avoid damaging the fan motor unit the drive must be kept in perfect working order The follo...

Page 25: ... case of drives with several belts the belts must be replaced at the same time This means that there must not be belts presenting different states of wear in the same drive system the number of belts must always match the number of races in this type of drive system the belt slack must be on the same side as shown in Hg 40 before they are tensioned 6 6 Heat recuperator 6 6 1 Crossover flow static ...

Page 26: ... rate This is the result of an uncontrolled increase in resistance in the air moving circuit which alters the fan s operating point The most frequent causes are excessively clogged filters formation of frost or ice on the front surface of the prefilters in particularly damp and cold climates on Units operating entirely with external air blockage of the intake grille s especially external air intak...

Page 27: ...s working life 7 SAFETY 7 1 SAFETY RELATED FEATURES OF AIR TREATMENT UNIT TCF Srl has fitted its Air Treatment Units with every possible safety feature to prevent accidents especially during start up and maintenance Some of these SAFETY FEATURES are listed below INSPECTION DOORS THAT CAN ONLY BE OPENED WITH A KEY are installed in the sections housing rotating parts and drives the GRATES and HOUSIN...

Page 28: ...ano di Granarolo E BO Declares that the following products AIR HANDLING UNIT Mod ZAE Customer Reference Order n Construction year is in compliance with the following Directives 2004 108 CE 2006 42 CE 91 368 CEE 93 68 CEE 2006 95 CE IT IS NECESSARY HOWEVER TO VERIFY THAT THE INSTALLATION AND THE DRIVE ARE CARRY OUT TO YOU CORRECTLY AND IN THE RESPECT OF DIRECTIVES EMC 2004 108 CE AND 2006 42 CE and...

Page 29: ...hould be sent prepaid to our headquarters and the replacement will be sent carriage forward Please note too that the warranty does not include the services of our personnel for the replacement of the part on site this cost is entirely for the installer s account On receipt of the returned material deemed to be defective an inspection will be carried out to establish whether the part reveals abnorm...

Page 30: ...30 ...

Reviews: