13. PROCEDURE FOR SELECTION OF SYSTEM TYPE
13. PROCEDURE FOR SELECTION OF SYSTEM TYPE
Several parameters of the MODU
CONTROL board have to be set, ba-
sed on the type of system the unit is
installed.
These changes of parameters are
summarised in the table below to
permit the installer to make the appro-
priate selections of the unit’s electro-
nic circuit board.
13.1. HOW TO MODIFY A USER
MENU PARAMETER
To access the
USER
setting press the
key and confi rm the password 000
pressing the key .
The display will show the parameters
of the
USER
index as three identifying
characters; the index remains displayed
for a second and then is replaced by the
value of the parameter it relates to.
To move to the following parameter
use the arrow keys . To modify a
parameter press the key , modify
the value using the arrow keys and
confi rm the modifi cation pressing the
key . To exit the menu press the key
13.2. HOW TO MODIFY AN
INSTALLER MENU PARAMETER
To enter and modify the
INSTALLER
menu follow the same procedure as
the USER menu above.
Password INSTALLER menu: 030
QUESTION
ANSWER
WHAT TO DO
(1) What type
of terminals are
installed in the
heating circuit?
• The unit is a coo-
ling only model
• Go to question 2
• Radiant panels
• Enter in parameter
StC
(index 3 menu USER) with the value of 35 °C
• Fan coil units or
low temperature
radiators
• Enter in parameter
StC
(index 3 menu USER) with the value of 45 °C (default
value)
• Other applications • Enter in parameter
StC
(index 3 menu USER) with the value of 55 °C
(2) Is the remote
control accessory
panel installed
(PR3)?
• Not installed
• Go to question 3
• Installed
• Enter in parameter
PAN
(index 9 menu INSTALLER) with the appropriate value:
Value (1):
• Season selection controlled from the unit circuit board
• ON/OFF control from the PR3
Value (2):
• Season selection controlled from the PR3
• ON/OFF control from the unit circuit board
Value (3)
:
• Season
selection controlled from the PR3
• ON/OFF control from the PR3
(3) Is domestic
hot water produc-
tion present?
• Not present
• Go to question 5
• Present
• Enter in parameter
ASA
(menu INSTALLER) with the value (1)
(4) In the do-
mestic hot water
circuit is a three
way diverting
valve present?
• Not present
• Go to question 5
• Present
• Enter in parameter
AAS
(index C menu INSTALLER) with the appropriate value
(in seconds): this parameter shows the reversing time for the three way diverting
valve in the circuit for the production of domestic hot water
(5) Is an ambient
thermostat pre-
sent?
• Not present
• No function
• Present
• This parameter enables a digital contact
ID
(shown on the electrical schematic
with the reference
TRA
) onto whWich to connect an ambient thermostat with
which to disable the compressors and electric heaters. Enter in parameter
trA
(index D menu INSTALLER)
, with the appropriate value selecting from:
1. Value (1 or 2): ENABLED
2. Value (0 or 3): DISABLED
3. It is reminded that the OPEN state of the contact represents
:
• stops compressors and heaters if the parameter value is set to 1
• stops compressors, pump and heaters if the parameter value is set to 2
• pump alarm (as in the previous software version), if the parameter value is set to 3