Parameter
Low Battery Protect
Value
On
Description
Enables or disables low battery protection with user programmable
shutdown, restart and delay values (standard respectively 10V, 12V and
5 seconds). Turning Low Battery Protect off, results in immediate inverter
shutdown when the battery voltage is less than 8.0V.
Configurable by
DIP switch (DIP 3) and Dashboard
Parameter
Automatic Stand By (ASB)
Value
Off
Description
Enables or disables ASB. If enabled, the inverter will jump to ASB mode
automatically, when the connected load power consumption drops
below a user programmable level. In ASB mode the inverter pulses it’s
output sinewave in order to detect when the connected load requires
more power again. While running in ASB mode, the Powersine Combi
itself draws significantly less current from the battery. As soon as the
load power demand increases again, the inverter will automatically jump
to continuous mode delivering uninterrupted power to the load. When
disabled, the inverter will always run in continuous mode, which is better
for critical loads like computers, clocks and AV equipment.
Configurable by
DIP switch (DIP 4) and Dashboard
Parameter
AC input voltage range (transfer switch)
Value
180V – 270V
Description
Input voltage range which is accepted by the Powersine Combi for
feeding through to the connected load. Two AC undervoltage values can
be set. An absolute undervoltage level which directly releases the AC
transfer switch when exceeded (factory setting = 150V), and a delayed
undervoltage level, which releases the AC transfer switch after a certain
delay (factory settings are 180V and 5 seconds). The charger stops
charging when the AC input voltage drops below 185V and restarts again
above 190V.
Configurable by
Dashboard
Parameter
AC input frequency range
Value
45Hz – 65Hz
Description
Input frequency range which is accepted by the Powersine Combi. Can be
set to full range (45Hz – 65Hz), or to a smaller range within the 45Hz
lower and 65Hz upper boundaries.
Configurable by
Dashboard
Parameter
AC Input Current Limit
Value
16.0A or 30.0A (depending on model)
Description
Represents the maximum continuous current that the Powersine Combi
will draw from the AC input source. To assure this, the Powersine Combi
will either reduce the charge current automatically, or (when enabled)
will activate the AC Input Power Boost feature which will supply the
additional power demand by running the inverter in parallel with the AC