Position 3
AGM
(also for
Optima
SpiralCell)
Absorption voltage = 14.70V / 29.40V / 58.80V
Float voltage = 13.65V / 27.30V / 54.60V
Equalize voltage = 15.50V / 31.00V / 62.00V
Max. bulk time = 8hrs
Max. absorption time = 4hrs
Position 4
Lead
Calcium
Absorption voltage = 14.80V / 29.60V / 59.20V
Float voltage = 13.50V / 27.00V / 54.00V
Equalize voltage = 15.80V / 31.60V / 63.20V
Max. bulk time = 16hrs
Max. absorption time = 8hrs
Position 5
LiFePO4
Absorption voltage = 14.40V / 28.80V / 57.60V
Float voltage = 13.80V / 27.60V / 55.20V
Equalize voltage = equalize not available
Max. bulk time = 12hrs
Max. absorption time = 12hrs
Position 6
Empty
Reserved for future use.
If selected anyway, the charger will return a battery error.
Position 7
Empty
Reserved for future use.
If selected anyway, the charger will return a battery error.
Position 8
Empty
Reserved for future use.
If selected anyway, the charger will return a battery error.
Position 9
Empty
Reserved for future use.
If selected anyway, the charger will return a battery error.
This manual will only describe the rotary selector settings. Configuration by TBS Dashboard
will be explained in the TBS Dashboard manual that comes with the TBSLink to USB
Communication Kit.