22
40
Charging temperature
compensation coefficient
0~30mV/
℃
(for 12V)
0~60mV/
℃
(for 24V)
0~120mV/
℃
(for 48V)
Step:1 mV/
℃
Default:18 mV/
℃
/(12V/cell)
41
Charging temperature
compensation control
0-Disable
1-Enable
Default:1
42
Low battery alarm
recover voltage
11.0~14.0V
Step:0.1V
Default:13.0V/(12V/cell)
43
Low SOC alarm threshold
15~90%
Step:1%
Default:15%
(≥Low SOC protect threshold)
44
Low SOC protect threshold
3~50%
Step:1%
Default:5%
(≤Low SOC alarm threshold)
45
Battery over temperature
threshold
25~65
℃
Step:1
℃
Default:55
℃
46
Battery equalization control
0-OFF
1-ON
Default:0
(Only in charge mode)
47
Battery equalization voltage
15.5~16.3V
Step:0.1V
Default:15.5V/(12V/cell)
48
Battery equalized time
30~90min
Step:5min
Default:30min
49
Battery Ah
50~5000Ah
Step:50Ah
Default:200Ah
50
BMS over voltage alarm
Control BMS
0-Display
1-Shield
Default:0
Summary of Contents for APOLLO MAXX Series