MPPT charge controller User Manual
2
6
.
FAQ
6.1 Fault code
Alarm level definition:
Fault: MPPT charger failure, into shutdown mode, no more charging.
Warning: MPPT charger warning, but also charging normally.
Type
ID
Name
Reason
Suggestion
Fault
01 V_bus_OV
PV voltage is too
high.
Check the string of PV array.
Make sure that the PV open
circuit voltage never higher than
the maximum range of MPPT
charger.
If it happens frequently, please
contact your dealer.
02 U_BAT_OV
Battery over voltage.
Check whether the battery
voltage setting of the charger is
consistent with the battery
configuration.
Change battery voltage of the
charger, or change battery
configuration.
If it happens frequently, please
contact your dealer.
03 U_Bat_OV_HD
04 Buck_Short Cut
Battery short circuit.
Check battery wiring. And
charger will return to normal
operation after the failure
disappears.
If no, please contact your dealer.
05 I_Buck1_OC
Buck1 of charger
over current.
Check whether the maximum
charging current is over range.
Check whether the charger
model setting is correct.
If the settings are correct,
please contact your dealer.
07 T_Board_OT
Temperature inside
the charger is too
high.
Check whether ambient
temperature is in range.
Check that the charger
installation environment is well
ventilated.
If the ambient temperature is too
high or is not ventilated well,
please improve its ventilation