2
Model 342 Tim Hortons
To the Installer
Air Cooled Units
DO NOT obstruct air intake and discharge openings:
The Model 342 air cooled unit requires a minimum of
3” (76 mm) air space around all sides. Install the
deflector to prevent recirculation of warm air.
Failure to allow adequate clearance can reduce the
refrigeration capacity of the freezers and possibly
cause permanent damage to the compressors.
Water Connections
(Water Cooled Units Only)
An adequate cold water supply must be provided
with a hand shut-off valve. On the underside rear of
the base pan, two 3/8” I.P.S. water connections for
inlet and outlet have been provided for easy
hook-up. 1/2” inside diameter water lines should be
connected to the machine. (Flexible lines are
recommended, if local codes permit.) Depending on
local water conditions, it may be advisable to install
a water strainer to prevent foreign substances from
clogging the automatic water valve. There will be
only one water “in” and one water “out” connection.
DO NOT install a hand shut-off valve on the water
“out” line! Water should always flow in this order:
first, through the automatic water valve; second,
through the condenser; and third, through the outlet
fitting to an open trap drain.
A back flow prevention device is
required on the incoming water connection side.
Please refer to the applicable National, State, and
local codes for determining the proper configuration.
Electrical Connections
In the United States, this equipment is intended to
be installed in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70-1987. The
purpose of the NEC code is the practical
safeguarding of persons and property from hazards
arising from the use of electricity. This code contains
provisions considered necessary for safety. In all
other areas of the world, equipment should be
installed in accordance with the existing local codes.
Please contact your local authorities.
FOLLOW YOUR LOCAL ELECTRICAL CODES!
Each unit requires one power supply for each data
label on the unit. Check the data label(s) on the
freezer for branch circuit overcurrent protection or
fuse, circuit ampacity, and other electrical
specifications. Refer to the wiring diagram provided
inside the electrical box for proper power
connections.
CAUTION: THIS EQUIPMENT MUST BE
PROPERLY GROUNDED! FAILURE TO DO SO
CAN RESULT IN SEVERE PERSONAL INJURY
FROM ELECTRICAL SHOCK!
This unit is provided with an equipotential
grounding lug that is to be properly attached to the
rear of the frame by the authorized installer. The
installation location is marked by the equipotential
bonding symbol (5021 of IEC 60417-1) on both the
removable panel and the equipment's frame.