16
9 - 11
PHOTOCELLS
Input for PHOTOCELLS OR SAFETY DEVICES active during closure (Normally
Closed contact); They stop the gate during closing and totally reopen it; they
temporarily stop the gate during opening in order to allow the obstacle to
be removed (if dip switch n° 3 set to ON). If there is more than one safety
device, connect all the NC contacts
IN SERIES
.
(9=COMMON, 11= PHOTOCELLS)
Note: the photocell transmitter must always be supplied by terminals
no. 13 - 15, since the safety system test (photo-test) is carried out on
it. To override the testing of the safety system, or when the photocells
are not used, set dip-switch no. 6 to OFF. If the photo-test is not
successful, the control unit will not operate.
12 - 13
2
nd
RADIO
CHANNEL
2nd RADIO CHANNEL output to be used for opening/closing another gate,
for controlling garden lights or for the “ZONE LIGHTING” function; (to be
programmed via TauApp);
Warning: to connect other devices to the 2nd Radio Channel (area
lighting, pumps, etc.), use an additional auxiliary relay.
14 - 15
GATE OPEN
LED
GATE OPEN LED output 24V AC - max. 3W; during opening of the gate
the warning light flashes slowly, when the gate is open it remains steadily
illuminated and during closure it flashes twice as fast. 14= 0Vac, 15= 24Vac;
16 - 18
TX
PHOTOCELL
24V AC 10 W POWER output for PHOTOCELL TX (only the one that
performs the Phototest) max. no. 1 photocell transmitter.
18= 0Vac, 16= 24Vac;
17 - 18
RX
PHOTOCELLS
24V AC 10W output to POWER THE RX AND/OR OTHER TX OF OHER
INSTALLED PHOTOCELLSPHOTOCELLS AND/OR EXTERNAL RECEIVERS,
etc.; connect a max. of 3 pair of photocells. 18= 0Vac, 17= 24Vac;
19 - 20
FLASHING
LIGHT
LEDS FLASHING LIGHT output 12V dc, 200mA max.
(NEGATIVE=19 - POSITIVE=20) The signal is already modulated for direct use.
Flashing frequency is double during closing;
21 - 22
AERIAL
433,92 MHz built-in RX antenna input; 21= EARTH, 22= SIGNAL;
M1
LIMIT
SWITCH
Quick coupling for LIMIT SWITCH connection (Normally Closed contacts).
Orange= Closure Limit Switch
(CLS)
,
ed= Opening Limit Switch
(OLS)
, grey= Common
(COM)
;
M2
ENCODER
Quick coupling for ENCODER connection. Blue= 0V DC
(GND)
, brown= 5V
DC
(+5V)
, white= ENCODER SIGNAL
(ENC)
;
FS1 - FS2
CAPACITOR
Faston for motor CAPACITOR connection;
M3
230V AC
MOTOR
Quick coupling for 230 Vac single-phase MOTOR connection common=
BLUE
(M-COM)
; closure= BROWN
(M-CL)
; opening= BLACK
(M-OP)
.
M4
AUX
Quick coupling for the connection of the
T-WIFI
and
T-CONNECT
devices
M5
MEMORY CARD
Quick plug-in for MEMORY CARD connection for transmitters codes.
5. LOGIC ADJUSTMENTS
TRIMMER
FR.
Motor torque adjustment. The trimmer is set to provide sufficient thrust to work the gate
without exceeding the limits established by current standards (EN 12453).
Turning the
trimmer clockwise (+) increases the motor torque, turning it anticlockwise (-) reduces it.
SENS
Adjustable only with ENCODER enabled (DIP 11 ON).
Obstacle detection additional adjustment;
Note: by rotating the TRIMMER FR. clockwise the sensitivity to obstacles of the oper
-
aor decreases
and therefore the thrust force increases;
vice-versa, by rotating it anti-
clockwise, t
he sensitivity to obstacles of the operator increases
and therefore the
thrust force decreases
.
WARNING: with the trimmer at maximum, the obstacle detection is disabled!!
T.C.A.
Automatic closing time adjustment from 5 to 120 seconds.
ENGLISH
Summary of Contents for K590M
Page 63: ...63 PORTUGUÊS ...