NOTES ON USING THE BIG18 WITH A SINGLE PHASE TO THREE PHASE INVERTER

1. With all power removed convert the D703 to a single phase control board by moving the wire one

terminal at SW1.

2. The motor wires connected at terminals 4, 5 and 6 on the D703 need to be connected to terminals

U, V and W on the inverter.

3. You will need two 240 volt relays. Connect terminal 4 (COM) on the D703 to one side of the coil of

both relays.

4. Connect 5 (OPEN) from the D703 to the other side of the coil of one relay.

5. Connect 6 (CLOSE) to the other side of the coil on the second relay.

6. Take the COM from the relay side of both relays to DCM (COM) on the inverter.

7. Take the N/O from the OPEN relay to FOR on the inverter.

8. Take the N/O from the COSE relay to REV on the inverter.

9. Connect 240 volts to the inverter at R, S and E and also to the D703 at terminals 1 and 2.

You are now ready to start testing your installation for motor for drive both ways and correct direction as

well as limits.

Summary of Contents for D703

Page 1: ...400 Vac single three phase motor Steuerplatine f r einphasigen dreiphasigen 230 400 Vac Motor Logique de commande pour moteur monophase triphase 230 400 Vca Panel de mandos para motor monof sico trif...

Page 2: ...upply 400Vac Power supply Flashing light 230Vac max 20W Cap 12 5 F 2 MASTER 20T BIG18QI Thermal protector OLS CLS Common Common Photocell Fixed safety edge Common Common Photocell Common Open Close St...

Page 3: ...ac 230Vac Radio connector Gate open warning light max 3W Antenna 2nd radio channel OLS Open limit switch CLS Close limit switch O C Open Close Ped Pedestrian Cap Capacitor TX Transmitter RX Receiver M...

Page 4: ...regulations and directives When designing its products TAU observes all applicable standards please see the attached declaration of conformity but it is of paramount importance that installers strict...

Page 5: ...wer 1 5 Kw ca Flashing light rapid fuse F1 5x20 F2A 250V AC Primary input line rapid fuse F2 F3 F4 5x20 F10A 250V AC Input voltage of motor circuits 230 400V AC Input voltage of auxiliary circuits 24V...

Page 6: ...s checked by the safety system the control unit will not work if it is disconnect ed To disable the safety system move dip switch 6 to OFF 19 20 CLS FCC CLOSE LIMIT SWITCH input normally closed contac...

Page 7: ...on is pushed the automatic system performs a complete opening or clos ing manoeuvre Note in the Man Present mode the PP input n 13 is disabled as is the radio receiver 4 not used 5 ENCODER On encoder...

Page 8: ...available voltage c_ Check that the NC contacts of the card are actually normally closed 5 green LEDs on d_ Set the dip 3 man present function to OFF dip 5 encoder to ON dip 6 phototest to OFF e_ Che...

Page 9: ...side of the coil of both relays 4 Connect 5 OPEN from the D703 to the other side of the coil of one relay 5 Connect 6 CLOSE to the other side of the coil on the second relay 6 Take the COM from the r...

Reviews: