background image

Rate of Rise Sensor 

(continued)

Mounting instructions:

 

Use the mounting tabs on the box (screws not provided) 

OR the included Dual Lock adhesive strips to attach the 

Rate of Rise Sensor to the ceiling. The best location for 
the sensor is at a high point where heat will build. The 

recommended mounting height is 10ft. The first sensor 

near a wall should be placed no more than 25ft away 
from the wall, additional sensors away from the wall can 

be spaced at 50ft (see fig.1) 

Sensors should be mounted no less than 4” from any 

corner and no more than 12” from ceiling (see fig. 2)

Mounting is possible above the height of 10ft but spacing 
between sensors and walls will decrease with additional 

height. (see fig. 3) or contact tattletale for specific mount

-

ing instructions).

When mounting sensors on ceilings with exposed joist al

-

ways mount sensors below, not between joist. (see fig.4) 

(fig. 1)

0 to 10’  

50’

10’ to 12’  

46’

12’ to 14’  

42’

14’ to 16’  

39’

16’ to 18’  

36’

18’ to 20’  

32’

20’ to 22’  

29’

22’ to 24’  

26’

24’ to 26’  

23’

26’ to 28’  

20’

28’ to 30’  

17’

sensor spacing

ceiling height

Sensor spacing decreases  
as mounting height increases 

(fig. 3)

(fig. 4)

(fig. 2)

NOTE:

 Do not mount sensors where they can be  

directly exposed to rain or snow.

Do not mount sensors in the direct path of hot or cold air flow. 

These conditions can cause alarm events and/or adversely 

affect the sensor’s sensitivity.