 Detector Dimensions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Schematic Diagram of Detector 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Outside Dimensions of Wall-embedded Type 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 Detector Installation Method 

* Make sure that the main power breaker is turned OFF and that alarm contact signal lines are open. 

Follow the procedure below to check detector installation, setting (adjustment) and operations. 

(1) Installing detecting box 

 Remove the outer cover. Using a flat-blade driver or similar tool, open the notches below the outer 

cover and remove it. 

 Remove the intermediate board. Loosen four M4 flat-head screws and remove the intermediate board 

(with circuit board) from the enclosure. 

* To install a detector in the wall-embedded scheme, refer to: Method of Installing the Wall-embedded Type. 

 Work on the enclosure. Decide wire insertion points and work on the enclosure for inserting wires as 

need arises. 

  Install  the  enclosure.  Using  the  mounting  holes  (four  5–mm-diameter  holes)  on  the  back  of  the 

enclosure, fix it in place. 

(2) Wiring the power supply, sensor, and alarm contact signal lines. 

 Insert wires into the enclosure. Using the back of the wall, wire protectors, or conduits, insert wires into 

the enclosure. 

 Attach crimp contacts to wires. By aligning the intermediate board (with circuit board) on the enclosure, 

adjust wire lengths. 
Note 1: Use crimp contacts    7.5 mm or less in diameter for use with an M3 or M4 screw. 
Note 2: Use crimp pliers matching the crimp contacts and wire size used. 

 Connect wires to the circuit board. Make secure connections according to the “terminal description” as 

shown below, using a flat-blade screwdriver. 

  To  improve  noiseproof  properties  and  resistance  to  static  electricity,  be  sure  to  make  grounding 

connections. 

Note 1: Bend crimp contacts about 45˚ as shown in “cross section.” 

                   

AD-AS-1AM-2

ON

   

 

 

 

 

0  1

  6

 

 
 
 
 
 
 
 
 
 
 
 
 
 
(3) Setting (adjustment) and checking 

 Checking settings: To change a setting, follow the instructions under: Detector Setting Method. 

  Checking  of  operations:  To  check  operations  at  time  of  installation,  refer  to:  Method  of  Operating 

Detector and Checking Detector Operations. 

(4) Completion of installation 

 Attaching the insulating sheet: Align the line on the insulating sheet to the terminal block and attach the 

sheet. 

 Fitting outer cover: After making sure that LEDs are not bent, attach outer cover. 

  Checking  operations  after  installation:  When  postponing  the  operation  test  due  to  power  supply 

condition  or  other  situations,  remove  the  outer  cover  and  follow  the  instructions  under:  Method  of 
Operating Detector and Checking Detector Operations for Testing. 

 
 
 
 
 

 Method of Installing Wall-embedded Type 

This detector can be installed in a wall-embedded finish after removal from enclosure. 
Refer to illustrations below to install detector using standard switch box, clamp fittings and retaining 
fittings. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

                                                                     

No.1AM-1206-01

 

Outer cover

Insulating sheet Circuit 

board

Enclosure

Intermediate 

board

Dustproof 

cover

Terminal block description 

Insulating sheet 

Crimp contact 

Crimp contact 

Cross section 

7.5 mm or less 

Examples of wall-embedded work execution (using standard boxes and fittings)

AD-AS-1AM-1

AD-AS-1AM-1

AD-AS-1AM-1

Position of fixing screw

Rear view (back of wall)

Side view 

(wall cross section)

Example of work execution with switch box

Example of work execution with clamp fittings

Example of work execution with retaining fittings

Panasonic DM8020K

Panasonic WN3993020

Panasonic WN3997

0 to 25 mm

7 to 18 mm

9 to 30 mm

Dimensions of mounting holes

98

88

98

10

5

98

94

48

1

2

4

120

33

15

63

74

AD-AS-1AM-1

45

8

2

9

8

Six 5x10-mm holes (for countersunk head screws)

7

8

6

6

98

Outside dimensions with

enclosure removed

Inside dimensions with

outer cover removed

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGE

DETECTOR

Tatsuta Electric Wire & Cable Co., Ltd.

<Manufacturer > 

   

Tatsuta Electric Wire & Cable Co., Ltd.

             

      System Division 
         

 

2-3-1 Iwata-cho, Higashi-Osaka, Osaka 578-8585   

                Tel: +81-6-6721-3335        Fax: +81-6-6725-0018 
     
            Sales department 
              3rd floor, Nihon-Seimei Kawasaki Bldg., 1-1, Minami-machi, Kawasaki Ward,   
              Kawasaki City, Kanagawa Prefecture    210-0015 
              Tel: +81-44-221-7691      Fax: +81-44-221-7695 

 

 

55

12

4

120

AD-AS-1AM

P O W E R

WATER LEAKAGE

CUT-OFF SENCOR

BUZZER STOP

R E S E T

WATER-LEAKAGE

DETECTOR

70

70

27

2

7

25

25

13

20

18

20

6

6

12 wire entry holes

Four 5-mm-diameter

mounting holes

Two 6x1.5-mm notches to permit outer cover removal

Tatsuta Electric Wire & Cable Co., Ltd.

CN1

Break detection
Alarm hold
Fail-safe
Buzzer

VR1 VR2

Power

Water 

leakage

Break

Sensitivity 

adjustment

ON OFF

Reset 

Buzzer stop

H

M

L

Buzzer 
volume

Detection 
sensitivity

Loud

High

100V

200V

Ground

Sensor (I)

 Sensor (O)

AC power input

NC

COM

NO

NC

COM

NO

Electric shock!

* Do not remove this 

protective sheet.

* Do not insert foreign 

bodies into the 

opening.

* Do not touch with wet 

hands.

Caution

Long-pushing the buzzer stop 

and reset buttons together 

(for 2 sec.) allows you to 

check how the detector circuit 

and relay operate.

Water leakage

Break

Water leakage alarm contact NC1 

Water leakage alarm contact COM1 

Water leakage alarm contact NO1 

Break alarm contact NC2 

Break alarm contact COM2 

Break alarm contact NO2 

N.C.(non-contact) 

Ground 

Sensor(I) 

Sensor(O) 

AC power 

AC100V

AC240V 