Detector Dimensions
Schematic Diagram of Detector
Outside Dimensions of Wall-embedded Type
Detector Installation Method
* Make sure that the main power breaker is turned OFF and that alarm contact signal lines are open.
Follow the procedure below to check detector installation, setting (adjustment) and operations.
(1) Installing detecting box
Remove the outer cover. Using a flat-blade driver or similar tool, open the notches below the outer
cover and remove it.
Remove the intermediate board. Loosen four M4 flat-head screws and remove the intermediate board
(with circuit board) from the enclosure.
* To install a detector in the wall-embedded scheme, refer to: Method of Installing the Wall-embedded Type.
Work on the enclosure. Decide wire insertion points and work on the enclosure for inserting wires as
need arises.
Install the enclosure. Using the mounting holes (four 5–mm-diameter holes) on the back of the
enclosure, fix it in place.
(2) Wiring the power supply, sensor, and alarm contact signal lines.
Insert wires into the enclosure. Using the back of the wall, wire protectors, or conduits, insert wires into
the enclosure.
Attach crimp contacts to wires. By aligning the intermediate board (with circuit board) on the enclosure,
adjust wire lengths.
Note 1: Use crimp contacts 7.5 mm or less in diameter for use with an M3 or M4 screw.
Note 2: Use crimp pliers matching the crimp contacts and wire size used.
Connect wires to the circuit board. Make secure connections according to the “terminal description” as
shown below, using a flat-blade screwdriver.
To improve noiseproof properties and resistance to static electricity, be sure to make grounding
connections.
Note 1: Bend crimp contacts about 45˚ as shown in “cross section.”
AD-AS-1AM-2
ON
1
2
3
4
0 1
4
5
6
9
(3) Setting (adjustment) and checking
Checking settings: To change a setting, follow the instructions under: Detector Setting Method.
Checking of operations: To check operations at time of installation, refer to: Method of Operating
Detector and Checking Detector Operations.
(4) Completion of installation
Attaching the insulating sheet: Align the line on the insulating sheet to the terminal block and attach the
sheet.
Fitting outer cover: After making sure that LEDs are not bent, attach outer cover.
Checking operations after installation: When postponing the operation test due to power supply
condition or other situations, remove the outer cover and follow the instructions under: Method of
Operating Detector and Checking Detector Operations for Testing.
Method of Installing Wall-embedded Type
This detector can be installed in a wall-embedded finish after removal from enclosure.
Refer to illustrations below to install detector using standard switch box, clamp fittings and retaining
fittings.
No.1AM-1206-01
Outer cover
Insulating sheet Circuit
board
Enclosure
Intermediate
board
Dustproof
cover
Terminal block description
Insulating sheet
Crimp contact
Crimp contact
Cross section
7.5 mm or less
Examples of wall-embedded work execution (using standard boxes and fittings)
AD-AS-1AM-1
AD-AS-1AM-1
AD-AS-1AM-1
Position of fixing screw
Rear view (back of wall)
Side view
(wall cross section)
Example of work execution with switch box
Example of work execution with clamp fittings
Example of work execution with retaining fittings
Panasonic DM8020K
Panasonic WN3993020
Panasonic WN3997
0 to 25 mm
7 to 18 mm
9 to 30 mm
Dimensions of mounting holes
98
88
98
10
5
98
94
48
1
2
4
120
33
15
63
74
O
N
1
2
3
4
AD-AS-1AM-1
45
8
2
9
8
Six 5x10-mm holes (for countersunk head screws)
7
8
6
6
98
Outside dimensions with
enclosure removed
Inside dimensions with
outer cover removed
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
Tatsuta Electric Wire & Cable Co., Ltd.
<Manufacturer >
Tatsuta Electric Wire & Cable Co., Ltd.
System Division
2-3-1 Iwata-cho, Higashi-Osaka, Osaka 578-8585
Tel: +81-6-6721-3335 Fax: +81-6-6725-0018
Sales department
3rd floor, Nihon-Seimei Kawasaki Bldg., 1-1, Minami-machi, Kawasaki Ward,
Kawasaki City, Kanagawa Prefecture 210-0015
Tel: +81-44-221-7691 Fax: +81-44-221-7695
55
12
4
120
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
70
70
27
2
7
25
25
13
20
18
20
6
6
12 wire entry holes
Four 5-mm-diameter
mounting holes
Two 6x1.5-mm notches to permit outer cover removal
Tatsuta Electric Wire & Cable Co., Ltd.
CN1
Break detection
Alarm hold
Fail-safe
Buzzer
VR1 VR2
Power
Water
leakage
Break
Sensitivity
adjustment
ON OFF
Reset
→
Buzzer stop
H
M
L
Buzzer
volume
Detection
sensitivity
Loud
High
100V
200V
Ground
Sensor (I)
Sensor (O)
AC power input
NC
COM
NO
NC
COM
NO
!
■
Electric shock!
* Do not remove this
protective sheet.
* Do not insert foreign
bodies into the
opening.
* Do not touch with wet
hands.
Caution
Long-pushing the buzzer stop
and reset buttons together
(for 2 sec.) allows you to
check how the detector circuit
and relay operate.
Water leakage
Break
Water leakage alarm contact NC1
Water leakage alarm contact COM1
Water leakage alarm contact NO1
Break alarm contact NC2
Break alarm contact COM2
Break alarm contact NO2
N.C.(non-contact)
Ground
Sensor(I)
Sensor(O)
AC power
AC100V
~
AC240V