1
2
3
4
5
6
7
8
O
N
1
2
3
4
5
6
7
8
O
N
Attached Drawing 6
Approved by Checked by Prepared by
Scale
Unit
Prepared on
-
/
-
mm
2011.08
N
a
m
e
Tatsuta Electric Wire & Cable Co., Ltd.
Instructions to operation
switchover DIP switch
AD-AS-10DRM
TTS-KS-W3155-3
No.
Factory
Operation
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1
2
3
4
5
6
7
8
Resistance
/
detection sensitivity switchover
OFF : Indicate the resistance of the sensor
ON : Indicate detection sensitivity
Main relay alarm hold
OFF : Not activated
ON : Activated
OFF : Not activated
ON : Activated
OFF : Not activated
ON : Activated
OFF : Not activated
ON : Activated
OFF : Not activated
ON : Activated
Individual relay alarm hold
Indicator LED
alarm hold
Fail- safe performance (main relay)
*relay operation when the sensor is normal.
Failure safe performance (individual relay)
*relay operation when the sensor is normal.
Abnormal contact operation switchover
OFF :
Abnormal contact operation when water leakage and break occur
ON : Abnormal contact operation only when break occurs
Buzzer operation setting
OFF : Activated
ON : Not activated
*Changing setting of SW2, allows operations such as indication and rela
Inadvertent setting change may result in unintended operations, so care should be taken.
*SW3 is the setting dispatched from the factory, do not change.
(For AD-AS-10DRM, please set
OFF)
setting
D
ra
w
in
g
N
o.