![Task Force Tips VORTEX 2 ER Manual Download Page 16](http://html2.mh-extra.com/html/task-force-tips/vortex-2-er/vortex-2-er_manual_3705797016.webp)
©Copyright Task Force Tips LLC 2018 - 2019
LIS-045 April 22, 2019 Rev01
TASK FORCE TIPS LLC
MADE IN USA • tft.com
3701 Innovation Way, Valparaiso, IN 46383-9327 USA
800-348-2686 • 219-462-6161 • Fax 219-464-7155
12.0 OPERATION AND INSPECTION CHECKLIST
BEFORE EACH USE
the nozzle must be inspected to this checklist:
1) There is no obvious damage such as missing, broken or loose parts, damaged labels etc.
2) Internal vanes are free of debris
3) Coupling is tight and leak free
4) Nozzle fl ow is adequate as indicated by pump pressure and nozzle reaction
5) Nozzle turns freely and adjusts pattern through full range with electric and manual control
BEFORE BEING PLACED BACK IN SERVICE
, nozzles must be inspected to this checklist;
1) All controls and adjustments are operational
2) There are no broken or missing parts
3) There is no damage to the nozzle that could impair safe operation (e.g. dents, cracks, corrosion or other defects)
4) The thread gasket is in good condition
5) The waterway is clear of obstructions
6) Nozzle is clean and markings are legible
7) Coupling is retightened properly
8) Nozzle is set to desired pattern
NFPA 1962: Standard for the care, use, inspection, service testing, and replacement of
fi
re hose, couplings, nozzles and
fi
re hose appliances. (2013
ed., Section 5.2.2). Quincy, MA: National Fire Protection Agency.
WARNING
Any nozzle failing any part of the checklist is unsafe for use and must have the problem corrected
before use or being placed back into service. Operating a nozzle that has failed the checklist is
a misuse of this equipment.