background image

Manual:

Pressure Relief Valve

LIA-202 October 4, 2004 Rev 0

©Copyright Task Force Tips, Inc. 2004

TASK FORCE TIPS, INC.

2800 East Evans Avenue, Valparaiso, IN 46383-6940

800-348-2686 • 219-462-6161 • Fax 219-464-7155

www.tft.com

TASK FORCE TIPS

TASK FORCE TIPS

This instruction manual is intended to familiarize firefighters and maintenance personnel with the operation, servicing and
safety procedures associated with the Pressure Relief Valve.

This manual should be kept available to all operating and maintenance personnel.

WARNING

Read instruction manual before use. Operation of this device without understanding the manual and
receiving proper training is a misuse of this equipment. A person who has not read and understood all
operating and safety instructions is not qualified to operate the Pressure Relief Valve.

INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

1.0 MEANING OF SAFETY WORDS

A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a particular
hazard. Per ANSI standard Z535.4-1998 the definitions of the three signal words are as follows:

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.

WARNING

CAUTION

DANGER

2.0 GENERAL INFORMATION

The Pressure Relief Valve may be set to any pressure between 50 and 200 p.s.i.. Its function is to protect the pump and the supply hose
from excess pressure. The relief valve may be mounted with its opening facing the front, back, right or left. A section of tubing or pipe
may be mounted on the round spout to route the water in any direction. To install the Pressure Relief Valve;

1) Install the O-ring in the groove on the Pressure Relief Valve.

2) Install four 7/16" bolts through the Pressure Relief Valve flange. Use a drop of thread locking compound on the threads of the bolts to
prevent them from coming loose.

3.0 RELIEF VALVE

SETTING

PRESSURE

To set the relief valve pressure turn the adjusting screw on the relief valve housing until the surface of the screw is

Do not cap or plug discharge opening.

even with the

desired pressure.

Adjusting
Screw

50 PSI

125 PSI

200 PSI

Reviews: