4

2.3 PATTERN CONTROL

TFT's Industrial and Masterstream nozzles have full pattern control from straight stream to wide fog. Turning the stream shaper
clockwise (as seen from the operating position behind the nozzle) moves the shaper to the straight stream position. Turning the stream
shaper counterclockwise will result in an increasingly wider pattern.

Since the stream trim point varies with flow, the stream trim point should be "trimmed" after changing the flow to obtain the straightest
and farthest reaching stream. To properly trim a stream, first open the pattern to narrow fog. Then close the stream to parallel to give
maximum reach. Note: Turning the shaper further forward will cause stream crossover and reduce the effective reach of the nozzle.

Note: Models are also available with linear (push/pull), remote electric or hydraulic actuation of the stream shaper.

FIG 1C - Masterstream 1000 Fixed Gallonage Nozzle

Halo Ring

Coupling

Stream Shaper / Bumper

Jam Nut

Baffle

FIXED

FLOW

2.4 USE WITH FOAM

The Industrial and Masterstream nozzles may be used with foam solutions. Refer to fire service training for the proper use of foam.

For Class B fires, lack of foam or interruption in the foam stream can cause a break in the foam
blanket and greatly increase the risk of injury or death. Assure that:

Application rate is sufficient (see NFPA 11 or foam manufacturer's recommendations).

Enough concentrate is on hand to complete task (see NFPA for minimum duration time
requirements).

Foam logistics have been carefully planned. Allow for such things as:

Storage of foam in a location not exposed to the hazard it protects.

Personnel, equipment and technique to deliver foam at a rapid enough rate.

Removal of empty foam containers.

Keeping clear path to deliver foam as hoses, other equipment and vehicles are deployed.

!
!

!

!
!
!
!

Improper use of foam can result in injury or damage to the environment. Follow foam
manufacturer's instructions and fire service training to avoid:

Using wrong type of foam on a fire, i.e. Class A foam on a Class B fire.

Plunging foam into pools of burning liquid fuels.

Causing environmental damage.

Directing stream at personnel.

!
!
!
!

There is a wide variety of foam concentrates. Each user is responsible for verifying that any foam
concentrate chosen to be used with this unit has been tested to assure that the foam obtained is
suitable for the purpose intended.

WARNING

WARNING

WARNING

2.4.1 FOAMJET LX WITH MASTERSTREAM NOZZLE

To increase the expansion ratio Task Force Tips "Foamjet LX" (model FJ-LX-M) may be used with the Masterstream nozzle. This low
expansion foam tube attaches and detaches quickly from the nozzle. Note: As expansion ratio is increased, the reach of the stream will
be decreased due to the greater amount of bubbles in the stream and their inability to penetrate the air. Generally, the reach with foam
is approximately 10 % less than with water only. Actual results will vary based on brand of foam, hardness of water, temperature, etc.

©Copyright Task Force Tips, Inc. 1998-2004

LIM-035 October 5, 2004 Rev02

Summary of Contents for INDUSTRIAL Series

Page 1: ... Deluge Nozzles With Fixed Selectable Flow 350 500 or 750 GPM 100 PSI 1300 2000 or 3000 LPM 7 BAR 700 KPA INDUSTRIAL 250 350 500 750 1000 GPM 100 PSI 1000 GPM MAX 100 PSI 1000 1500 2000 2500 3000 4000 LPM 7 BAR 700 KPA 1200 1800 2400 3000 3600 4800 LPM 10 BAR 1000 KPA 500 1000 1500 2000 2500 LPM 7 BAR 700 KPA 4000 LPM MAX 7 BAR 700 KPA MASTERSTREAM 1000 SELECTABLE MASTERSTREAM 1000 FIXED WARNING N...

Page 2: ...ean far reaching straight stream They are adjustable from straight stream to a dense fog pattern Their rugged construction is compatible with the use of fresh water as well as fire fighting foam solutions A summary of each nozzle s characteristics is shown in the tables below This equipment is intended for use by trained personnel for firefighting Their use for other purposes may involve hazards n...

Page 3: ...y be carried back to the nozzle will depend on the following factors Voltage of the line or equipment Distance from the nozzle to the line or equipment Size of the stream Whether the stream is solid or broken Purity of the water 2 WARNING 1 2 Electrostatic Hazards of Foam Blanketing Operations by Peter Howels Industrial Fire Safety July August 1993 The Fire Fighter and Electrical Equipment The Uni...

Page 4: ... to complete task see NFPA for minimum duration time requirements Foam logistics have been carefully planned Allow for such things as Storage of foam in a location not exposed to the hazard it protects Personnel equipment and technique to deliver foam at a rapid enough rate Removal of empty foam containers Keeping clear path to deliver foam as hoses other equipment and vehicles are deployed Improp...

Page 5: ...zzle s baffle Figure 3 gives relationship of flow and pressure for various orifice sizes The Masterstream 1000 Selectable Nozzle allows the user to select one of several orifice sizes by turning a knob at the front of the nozzle An indicator on the knob shows which flow has been selected Figure 3 gives relationship of flow and pressure for various orifice sizes 0 0 20 40 4 60 80 8 100 120 12 140 1...

Page 6: ...Q D P Flow water with a smooth bore nozzle and record the nozzle s size pitot pressure and in line pressure gauge reading The smooth bore nozzle s flow is calculated from the Freeman formula Where F 29 71 for English units GPM INCHES PSI F 667 for metric units LPM MM BAR Note 1 BAR 100 KPA is smooth bore nozzle flow in GPM or LPM is nozzle exit diameter in INCHES or MM is pitot pressure in PSI or ...

Page 7: ...1000 GPM at 100 PSI For other orifice sizes and pressures the graphs may be interpolated Notes on trajectory graphs Graphs show approximate effective stream trajectory at 30 degrees elevation in no wind conditions Distance to last water drops approximately 10 farther Trajectories shown are for water The addition of foam is expected to decrease the reach by approximately 10 Tail or head winds of 20...

Page 8: ...limited warranty the claimant must return the equipment to TFT at 2800 East Evans Avenue Valparaiso Indiana 46383 within a reasonable time after discovery of the defect TFT will examine the equipment If TFT determines that there is a defect attributable to it TFT will correct the problem within a reasonable time If the equipment is covered by this limited warranty TFT will assume the expenses of r...