Tapeswitch PRSU/4 Operating Instructions Manual Download Page 4

 

© 

Copyright (2021) 

All

 rights reserved. Changes, which serve technical improvements are reserved.

 

 

PRSU/4, PRSU/5 Operating Instructions Manual (Revision 3.0) 

 

 

Device Startup Verification 

 

 
Before creating any electrical connection to the device´s relay channels,   
RESET circuit, or switch monitoring terminals, select a power supply with ap-
propriate voltage settings and ensure its output is set OFF. 

 

 

 

Connect the power supply output (with appropriate input power source; see  
requirements listed on Page 10 of this manual) to the PRSU/4 or PRSU/5 
power input terminals (A1, A2), then apply the correct voltage for the device 
and verify that the “Power” LED illuminates green. 
 

 

 

 

Turn OFF power from the supply and make the appropriate connections to 
the switch monitoring channels, relays and RESET circuit according to the 
configuration guidelines laid out on Pages 5 through 7 of this manual. 

 

 

 

 
When the correct configuration is implemented and power is again applied, 
monitoring of the switches/sensors will only occur once a RESET signal is  
received by bridging S33 and S34 with an appropriately rated wire. See 
Pages 5 through 7 of this manual for more information. 

 

 
 
After the RESET signal is received and the monitored switch is in the  
unactuated state, the relay contacts (13 

 14), (23 

 24) and (33 

 34) will 

close. Contacts (41 

 42) will open. 

 
 

 

 

Recommended Limits

 

 
Performance of the PRSU/4 and PRSU/5 is limited according to the values 
listed on Page 10 of this manual. 

In particular, a 200Ω limit on short-circuit 

(actuated state) series resistance is required for four-wire, fail-safe  
applications. The overall series resistance of different products, cables and 
layouts can vary greatly. To ensure that a particular application will require 
only a single PRSU/4 or PRSU/5, the following rule-of-thumb guidelines can 
be used: 
 
 

Recommended Application Limits 

Product Type 

Maximum Area 

Maximum Length 

ControlMat, ArmorMat, DPM 

100ft² 

N/A 

Sensing Edge Products (all) 

N/A 

200ft 

Ribbon Switches 

N/A 

200ft 

SE-45, SE-75, SE-C Bumpers 

N/A 

200ft 

All values listed assuming 20AWG/4, Ø3/16, lead cable @ 500ft max. 

 

Table 1: Safety Product Recommended Limits 

    

 

 

    

Summary of Contents for PRSU/4

Page 1: ...plants who are familiar with the safety instructions and safety regulations Skilled personnel who build install maintain and operate safety equipment in plants and machinery Symbol Key These operating...

Page 2: ...egulations for safety at work and accident prevention and who have read this manual s content in full Installation assembly and maintenance of electrical equipment is only permitted by specialized sta...

Page 3: ...ons Manual Revision 3 0 PRSU 4 PRSU 5 Output Contacts A1 A2 13 14 23 24 33 34 41 42 S33 S34 S11 S12 S21 S22 Power supply inputs Safety relays normally open Auxiliary relay normally closed RESET mode c...

Page 4: ...onitoring of the switches sensors will only occur once a RESET signal is received by bridging S33 and S34 with an appropriately rated wire See Pages 5 through 7 of this manual for more information Aft...

Page 5: ...otch on the rear of the unit for DIN Rail attachment Electrical Connections Wire the device based on which of the following options best suits the target application RESET Mode Control Wiring 1 Automa...

Page 6: ...he closure is broken and a RESET signal is manually generated by the operator via a mechanical N O pushbutton or switch 3 Conditional In this operating mode the RESET signal cannot propagate unless al...

Page 7: ...to de energize Warning For this configuration to work as intended the series resistance between each end of the sensor s conductors cannot exceed 10 Additionally the short circuit resistance between...

Page 8: ...no terminal of the device is connected to a live voltage before continuing 2 Unscrew terminals A1 and A2 from the device before removing any other connections 3 One at a time free connections from the...

Page 9: ...es In cases where either one or both Channel LEDs is OFF during normal operation please verify that the device is properly wired If the problem persists the device is no longer capable of service Reti...

Page 10: ...ifetime 105 switching cycles DC 24V 2A 105 switching cycles DC 24V 2A Creeping Distance and Clearance EN 50178 at pollution grade 2 over voltage category 3 250V Basis isolation over voltage category 3...