18
1.2.5
Overload protection
Location
Protection
Mains supply
Hydraulic-magnetic circuit breaker
Control unit output
Hydraulic-magnetic circuit breaker
Control unit control/metering
T4A HRC 32mm fuse
Voltage input
2xT250mA HRC 32mm fuses
1.3
Functions
1.3.1
Output
The output has three ranges. The highest currents are available on the lowest voltage outputs.
When testing, start with the lowest output voltage output. If the required test current cannot be
achieved (because the impedance of the line is high) use a higher voltage output.
Output unit
Open Circuit
Voltage
Continuous
current
Intermittent current
5 min on/
15 min off
Maximum
current
NLU75/80
75V
40A
80A
100A*
150V
20A
40A
40A
300V
10A
20A
20A
*100A available for short periods
Each output is rated for a continuous current and for higher intermittent currents. The maximum
ON time for intermittent currents is enforced by the unit, and the output will be switched off if the
rating is exceeded. The display will then show the following message until the green OFF button
is pressed to clear the trip condition:
Figure 1.8 Output tripped
!
NOTE
If the metering cable is not connected between the control unit and the external
output unit, the ammeter will not function, and the output will not switch on when the
output
ON
push-button is pressed. The metering cable between the control and
external output unit acts as an interlock circuit.
Output tripped
Press Green to Reset
Summary of Contents for Z-OVR
Page 4: ......
Page 10: ...10 A B C D E F G H I J 1 1 2 Output unit Figure 1 2 Output unit front panel ...
Page 17: ...17 1 2 4 System connections Figure 1 7 System connections ...
Page 31: ...31 Figure 3 2 Phase A B test Figure 3 3 Phase B C test ...
Page 32: ...32 Figure 3 4 Phase C A test Figure 3 5 Parallel test to earth ...
Page 36: ......
Page 38: ......
Page 40: ......
Page 42: ...42 Drawings Required A3 001778 latest issue Z OVR A3 001770 latest issue NLU75 80 ...