15
Output cables
Length
Purpose
Rating
Output cable phase A
(red)
12mm² current injection
terminated in 6mm
connector
6mm² voltage sense
terminated in 4mm
shrouded plug
10m
Duplex lead fitted with Kelvin
clamp for overhead line
connection.
Max conductor size 80mm
diameter.
80A
CAT I
300V*
Warning
Output cable phase B
(yellow)
12mm² current injection
terminated in 6mm
connector
6mm² voltage sense
terminated in 4mm
shrouded plug
10m
Duplex lead fitted with Kelvin
clamp for overhead line
connection.
Max conductor size 80mm
diameter.
80A
CAT I
300V*
Warning
Output cable phase C
(blue)
12mm² current injection
terminated in 6mm
connector
6mm² voltage sense
terminated in 4mm
shrouded plug
10m
Duplex lead fitted with Kelvin
clamp for overhead line
connection.
Max conductor size 80mm
diameter.
80A
CAT I
300V*
Warning
Output cable ground
(green)
12mm² current injection
terminated in 6mm
connector
6mm² voltage sense
terminated in 4mm
shrouded plug
10m
Duplex lead fitted with Kelvin
clip.
Max jaw opening 27mm.
80A
CAT I
300V*
Warning
*voltage
ratings
Warning
The voltage ratings shown relate to the cable and 4mm/6mm connectors to
connect to the output unit. The cables are terminated in
un-insulated
clamps for
connection to lines that must
NOT
be handled whilst the output is on.
Make all connections to the test object with the supply off (supply switch in the
off position) and the cables unplugged from the output unit.
Summary of Contents for Z-OVR
Page 4: ......
Page 10: ...10 A B C D E F G H I J 1 1 2 Output unit Figure 1 2 Output unit front panel ...
Page 17: ...17 1 2 4 System connections Figure 1 7 System connections ...
Page 31: ...31 Figure 3 2 Phase A B test Figure 3 3 Phase B C test ...
Page 32: ...32 Figure 3 4 Phase C A test Figure 3 5 Parallel test to earth ...
Page 36: ......
Page 38: ......
Page 40: ......
Page 42: ...42 Drawings Required A3 001778 latest issue Z OVR A3 001770 latest issue NLU75 80 ...