31
Loading unit
Metering range
Range full scale
Approximate timer
start/stop current
None
Secondary Injection
10A
10A
2A
20A
20A
4A
100A
100A
20A
NLU5000
10%
500A
100A
50%
2500A
500A
100%
5000A
1000A
NLU2000
10%
200A
40A
50%
1000A
200A
100%
2000A
400A
NLU200
10%
20A
4A
50%
100A
20A
100%
200A
40A
2.3.1.6 Pulse Mode
Pulse mode may be used to generate high current pulses into the test object. The electronic
trips are disabled in pulse mode, and the output current is only limited by the circuit
impedance. This is useful for setting the current when testing thermal devices and testing
instantaneous trips.
2.3.2
General Procedure for Timing Tests
The procedure for timing is the same whether an external loading unit is connected or the
secondary current injection output from the PCU1 is used.
2.4.2.1 Connections
Ensure that the unit is switched off and the test object is isolated and grounded before making
any connections.
Connect the loading unit to the control unit as shown in figure 2.1. In the case of the
secondary injection output, make the connections shown in figure 2.2.
Set the ammeter range switch to one of the main output ranges (10%, 50% or 100%).
Connect the output cables to the desired output on the loading unit and to the test object.
Connect the supply lead to the mains and switch the main supply switch on. The display will
come on, showing the unit type and loading unit type whilst starting up.