background image

                                                                                                       TX7322 Addressable Sounder Base 

 

 

        Installation & Operation Manual  

In dual-encoding mode, the Addressable Sounder Base has two addresses. It can be started, 

silenced and stopped by a controller. As in the non-coding mode, it can be controlled by a 

detector which mounted on it. It can also be controlled by other front-end devices. In the 

linkage control process, the Addressable Sounder Base will make a warning tone firstly when 

the fire occurred. And then it will make an alarm tone when the fire has confirmed by the 

controller. 

 

The encoding mode of the Addressable Sounder Base can be set by a programming tool. As 

shown in figure 11, the option corresponding to the number will be selected when a number 

is  pressed  at  the interface shown in Figure 6. And then click the button  “write”.  The  word 

“Success”  or  “Fail”  on the screen  means  that the success  or not of the encoding mode 

setting, as shown in figure 12 and figure 13.  

Success

Fail

No Cod

Single

Strobe

Typ

Code

Dual

Saving

Sound

 

Fig.11 

Encoding mode setting     Fig.12 Success to setting               Fig.13 Fail to setting 

 

Note: 

The 

programming tool

 can still read the address of the Addressable Sounder Base in 

non-coding mode. But the controller can not check the presence of it.

 In dual address 

mode, the sounder will generate the unique next higher number for the second address for 

example: In single address mode the address number is 15, when change to dual address 

mode the address numbers will now be 15 and 16.  

 

Warning:  Dual address mode may  cause Duplicate address fault on the panel and may 

affect the operation of the next device  with conflicted address number if  not carefully 

arrange the loop addressing. 

 

3.4 Tone Setting      

The  TX7322  Addressable Sounder Base  has  16  kinds  of  different alarm tone  and a kind of 

warning  tone.  The Tones of it can be change according to the project requirement by  a 

programming tool. The detailed parameters of different tone are shown in Table 1. 

 

Table 1 Detailed parameters of different tone 

Paramete

Tone 

Code 

dB(A) Output 

(1m) 

Description 

01 

80.2 

970Hz 

02 

84.8 

800Hz / 970Hz @ 2Hz 

03 

85.5 

800Hz -970Hz @1Hz 

                                                                                                                               4050100446-Rev1.0-0917                                                                      

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

Summary of Contents for TX7322

Page 1: ...TX7322 Addressable Sounder Base Installation and Operation Manual TANDA UK Technology Copyright 2017 All right reserved...

Page 2: ...Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your loca...

Page 3: ...on and Wiring 5 3 Addressable Sounder Base Configuration 6 3 1 Preparation 6 3 2 Parameter setting 6 3 3 Encoding Mode Setting 7 3 4 Tone Setting 8 3 5 Read Configuration 10 4 General Maintenance 10 5...

Page 4: ...tibility problem 1 2 Feature and Benefits EN54 3 compliance Built in MCU processor and digital addressing 17 tones Programmable sound output Encoding modes such as Non coding Mode Single encoding Mode...

Page 5: ...als connection diagram as shown in Figure 1 2 The bottom structure of the Addressable Sounder Base as shown in Figure 2 Install the Addressable Sounder Base on the TX3980 type base with the installati...

Page 6: ...Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Parameter setting 1 Connect the programming cable to Z1 and Z2 terminals as shown in Figure 5 Pre...

Page 7: ...s such as non coding mode single encoding mode and dual encoding mode Different encoding modes correspond to different ways of operation It can be change the encoding mode by a programming tool Non en...

Page 8: ...ding mode setting Fig 12 Success to setting Fig 13 Fail to setting Note The programming tool can still read the address of the Addressable Sounder Base in non coding mode But the controller can not ch...

Page 9: ...5s 0 25s off 17 17 78 9 800Hz 1s off 1s on Pre alarm 1 Attach the programming tool to 1 and 6 Terminals of Addressable Sounder Base Press Power to switch on the unit 2 Switch on the programmer then pr...

Page 10: ...cting the maintenance and make sure to enable the alarm warning device and confirm if up and running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Gu...

Page 11: ...0 7 77 4 75 5 45 71 1 69 8 75 1 72 7 75 70 6 73 9 76 3 77 8 105 71 2 70 1 74 1 75 4 135 72 0 70 4 77 5 72 3 165 70 7 70 8 74 7 76 3 Limitation of Addressable Sounder Base The alarm warning device cann...

Page 12: ...other components of the system must be repaired and or replaced immediately as they fail This product is not approved to EN54 23 Beacon Functionality and must not be used as a visual alarm device or...

Reviews: