background image

                                                                                                       TX7320 Addressable Sounder 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100271-Rev1.0-1215                                                                       

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

Figure 10 

 

Figure 11 

 

3.4 Typical and Saving Mode  

When  Sounder  is  configured  to  Saving  Mode  the  recommended  wiring  is  loop  powered 
[Figure 2] within the limit of 20 units per loop and subject to the total calculated current load 
in particular loop. If Sounder is configured to Typical Mode, it requires external power supply 
[Figure 3] installer should consider additional power cable.  
 

1.

 

Attach the programming cable to 1 and 6 Terminals of sounder. Press 

“Power”

 to switch-on 

the unit.  

2.

 

Switch-on the programmer, then press button 

“3” 

to enter to 

Configuration mode

 (Figure 10).  

3.

 

Input  the 

“3”

  for 

Typical

  mode  or 

“4”

  for 

Saving

  mode  then  press 

“Write”

  to  change  the 

setting into the desire mode (Figure 11).   

 
Note:

  If  display 

“Success”, 

means  the  entered  mode  is  confirmed.  If  display 

“Fail”,

  means 

failure to program the mode.  

 
Warning

:  Under  saving  mode  loop  powered  up  to  20  sounder  maximum  per  loop  is  the 

recommended. 

 

 

 

 

 

 

 

 

 

 

4.

 

Press 

“Exit” 

key to go back Main Menu. Press 

“Power”

 key to switch off the programmer.  

 

3.5 Sounder Type  

1.

 

Attach the programming cable to 1 and 6 Terminals of sounder. Press 

“Power”

 to switch-on 

the unit.  

2.

 

Switch-on the programmer, then press button 

“3” 

to enter to 

Configuration mode

 (Figure 12).  

3.

 

Input the 

“5”

 for 

Strobe

 type or 

“6”

 for 

Sounder

 type, then press 

“Write”

 to change the setting 

into the desire mode (Figure 13).   

Note:

  If  display 

“Success”, 

means  the  entered  type  is  confirmed.  If  display 

“Fail”,

  means 

failure to program the type.  No use for TX7320 to select 

Strobe

 Mode. 

4.

 

Press 

“Exit” 

key to go back Main Menu. Press 

“Power”

 key to switch off the programmer.  

 
 
 
 
 
 
 
 
 

1. Read 

2. Write                  T 
3. R/W Config  

4. Set 

 

 

Read Description  

Typ

: Typical mode, the 

sounder device consume 
4mA [Default] 

 

Saving

: Low current 

consumption at 4mA 
 

 

 

 

 

 

 

 Single       

 Dual 

 Typ         

Saving   

Strobe        

Sound 

 

 

 

Summary of Contents for TX7320

Page 1: ...TX7320 Addressable Sounder Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Page 2: ...nstalling the Sounder to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal...

Page 3: ...pecification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Configuration 6 3 1 Preparation 6 3 2 Addressing 6 3 3 Single and Dual Address Mode 7 3 4 Typical...

Page 4: ...ntelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in MCU processor and di...

Page 5: ...he correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as shown in Figure 2 3 Verify the device number or other device p...

Page 6: ...ts Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld progra...

Page 7: ...will produce simultaneously audible signal according to the pre defined tone Table 1 Tone 14 is the default tone and will stop if the panel is reset 1 Attach the programming cable to 1 and 6 Terminals...

Page 8: ...11 Note If display Success means the entered mode is confirmed If display Fail means failure to program the mode Warning Under saving mode loop powered up to 20 sounder maximum per loop is the recomme...

Page 9: ...3 3 5s on 0 5s off 7 07 106 6 101 4 2850Hz 0 5s on 0 5s off 3 1 5s off 8 08 106 1 102 3 2850Hz 0 4s on 0 3s off 9 09 99 7 96 6 550Hz 0 7s 1000Hz 0 33s 10 10 105 7 100 8 1500Hz 2700Hz 3Hz 11 11 102 3 9...

Page 10: ...f display Fail means failure to program the tone Figure16 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 7 Read Con...

Page 11: ...running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is loose The a...

Page 12: ...27 5V Min 18V 15 87 3 85 1 89 3 98 0 76 7 76 1 76 1 77 3 45 87 3 83 9 86 7 84 4 75 4 76 8 81 0 81 2 75 84 2 81 1 94 3 90 9 81 9 83 7 81 4 82 8 105 84 1 82 4 90 9 87 7 79 5 81 2 79 4 80 2 135 89 7 87 6...