                                                                                                       TX7320 Addressable Sounder 

 

 

        Installation & Operation Manual  

                                                                                                                               4050100271-Rev1.0-1215                                                                       

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

      

 

Figure 8 

 

Figure 9 

 

3.3 Single and Dual Address Mode 

Single  address  is  commonly  used  to  program  immediate  Evacuate  tone  while  the  dual 
address used for programming Pre-alarm and Evacuate tones respectively in a given period 
of time.  
 

In Single Address Mode  

When in action (Evacuation stage), the sounders will produce simultaneously audible signal 
according to the pre-defined tone (Table 1- Tone 14 is the default tone) and will stop if the 
panel is reset.  
 

In Dual Address Mode  

When  In  action  the 

1

st

  Address  sounder

  (Pre-alarm  Stage),  will  produce  simultaneously 

audible signal according to the pre-defined tone (Table 1- Tone 17 is the default tone). This 
will run continuously according to the pre-defined time unless the panel is being reset before.  
When  the  delay  time  is  over  the  1

st

  address  sounder  will  stop  then  immediately,  the 

2nd 

address sounder 

(Evacuate Stage) will produce simultaneously audible signal according to 

the pre-defined tone (Table 1- Tone 14 is the default tone) and will stop if the panel is reset.   
 

1.

 

Attach the programming cable to 1 and 6 Terminals of sounder. Press 

“Power”

 to switch-on 

the unit.  

2.

 

Switch-on the programmer, then press button 

“3” 

to enter to 

Configuration mode

 (Figure 8).  

3.

 

Input  the 

“1”

  for  Single

 

Address  mode  or 

“2”

  for  Dual  Address  mode  then  press 

“Write”

  to 

change the setting into the desire mode (Figure 9).   

Note:

  If  display 

“Success”, 

means  the  entered  mode  is  confirmed.  If  display 

“Fail”,

  means 

failure to program the mode.  
In  Dual  address  mode,  the  sounder  will  generate  the  unique  next  higher  number  for  the 
second address for example: In single address mode the address number is 15, when change 
to dual address mode the address numbers will now be 15 and 16.  
 

Warning:

  Dual  address  mode  may  cause  Duplicate  address  fault  on  the  panel  and  may 

affect  the  operation  of  the  next  device  with  conflicted  address  number  if  not  carefully 
arrange the loop addressing. 

 

 
 
 
 
 
 

 

 

 

 

 

  

 

 

4.

 

Press 

“Exit” 

key to go back Main Menu. Press 

“Power”

 to switch off the programmer.  

 
 

1. Read 
2. Write                  T 

3. R/W Config  

4. Set 

 

 

 Single      

Dual

 

 Typ              

Saving

   

Strobe         

Sound

 

 

 

Configure Description  

 Single 

[Default] 

 Dual

 

 

 

Summary of Contents for TX7320

Page 1: ...TX7320 Addressable Sounder Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Page 2: ...nstalling the Sounder to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal...

Page 3: ...pecification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Configuration 6 3 1 Preparation 6 3 2 Addressing 6 3 3 Single and Dual Address Mode 7 3 4 Typical...

Page 4: ...ntelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in MCU processor and di...

Page 5: ...he correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as shown in Figure 2 3 Verify the device number or other device p...

Page 6: ...ts Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld progra...

Page 7: ...will produce simultaneously audible signal according to the pre defined tone Table 1 Tone 14 is the default tone and will stop if the panel is reset 1 Attach the programming cable to 1 and 6 Terminals...

Page 8: ...11 Note If display Success means the entered mode is confirmed If display Fail means failure to program the mode Warning Under saving mode loop powered up to 20 sounder maximum per loop is the recomme...

Page 9: ...3 3 5s on 0 5s off 7 07 106 6 101 4 2850Hz 0 5s on 0 5s off 3 1 5s off 8 08 106 1 102 3 2850Hz 0 4s on 0 3s off 9 09 99 7 96 6 550Hz 0 7s 1000Hz 0 33s 10 10 105 7 100 8 1500Hz 2700Hz 3Hz 11 11 102 3 9...

Page 10: ...f display Fail means failure to program the tone Figure16 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 7 Read Con...

Page 11: ...running 6 Perform the maintenance on semi annually or depending on the site conditions 5 Troubleshooting Guide What you notice What it means What to do Address not enrolling The wiring is loose The a...

Page 12: ...27 5V Min 18V 15 87 3 85 1 89 3 98 0 76 7 76 1 76 1 77 3 45 87 3 83 9 86 7 84 4 75 4 76 8 81 0 81 2 75 84 2 81 1 94 3 90 9 81 9 83 7 81 4 82 8 105 84 1 82 4 90 9 87 7 79 5 81 2 79 4 80 2 135 89 7 87 6...