TX7210 Addressable Single Input/Output Module
Installation & Operation Manual
4050100267-Rev1.6-0916
TANDA UK
Specifications are subject to change without prior notice
10
3.6 Read Configuration
1.
Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press
“Power”
to switch-on
the unit.
2.
Switch-on the programmer, then press button
“Read”
or
“1”
to enter to Read
mode (Figure
16). The programmer will display the configuration after few seconds. (Figure 17).
3.
Press
“Exit”
key to go back Main Menu. Press
“Power”
key to switch off the programmer.
4 General Maintenance
1.
Inform the suitable personnel before conducting the maintenance.
2.
Disable the interface module on the control panel to prevent false alarm.
3.
Do not attempt to repair the circuitry of the interface module, it may affect the operation to
respond to a fire condition and will void the manufacturer’s warranty.
4.
Use a damp cloth to clean the surface.
5.
Notify again proper personnel after conducting the maintenance and make sure to enable
the interface module and confirm if up and running.
6.
Perform the maintenance on semi-annually or depending on the site conditions.
1. Read
2. Write T
3. R/W Config 7
4. Set
Address: 001
External
Input Check
-˃
Output
UnCheck
ID:123456789012
˂-
Parameter Description
Address
: Unique number
assigned
1Y Self-Feedback Mode
2N External-Feedback Mode
(Default)
3Y Enable Input Check Mode
4N Disable Input Check Mode
(Default)
5Y Enable Output Check Mode
6N Disable Output Check
Mode
[Default]
ID
: Device serial number
Parameter Description
5Y Enable Output Check Mode
6N Disable Output Check Mode
(Default)
1. Read
2. Write T
3. R/W Config 7
4. Set
Figure 14
Figure 15
Feedback 1Y 2N
Input Check 3Y 4N
Output Check 5Y 6N
Figure 16
Figure 17