AIR-IQ2 AIRFLOW MEASUREMENT SOLUTION

T.A. Morrison & Co. Inc.   |   P.O. Box 157 Smiths Falls Stn Main, Ontario, Canada K7A 4T1   |   800 561 3449   |   Fax: 800 668 8476   |   tamcodampers.com

EBTRON, Inc.   |   1663 Hwy. 701 S., Loris, SC USA 29569   |   800.2EBTRON (232.8766)   |   Fax: 843.756.1838   |   www.ebtron.com

AIR-IQ2 INS

TALL GUIDE_2022_04

CALL TAMCO CUSTOMER SERVICE WITH ANY QUESTIONS CONCERNING TAMCO DAMPERS

1-800-561-3449

INSTALLATION GUIDELINES

• 

When the AIR-IQ2 unit is viewed from damper side and labels on blades are right side up, unit orientation is Front/Top end up. 

• 

When viewed as Front/Top end up, right hand (RH) has drive rod as shown. Left hand (LH) has drive rod on left. 

• 

The complete AIR-IQ2 unit can be installed vertically with the damper orientation being right side up, or lying flat. 

• 

Ensure that the AIR-IQ2 Unit is installed allowing for future access to the EBTRON transmitter, probes, damper side linkage, as well as the 

damper jumper bracket. 

• 

Duct work construction and bracing must be sufficient to support the AIR-IQ2 unit. Do not use the AIR-IQ2 unit to square up the duct. The 

system must support the AIR-IQ2 unit. The AIR-IQ2 unit cannot support the system. For AIR-IQ2 units with two damper sections, ensure that 

each section is properly braced and supported. 

• 

For single-section, vertical blade applications, the AIR-IQ2 unit must be installed so that the linkage and probe cables are located at the top. 

•  A 12" long, hexagonal steel drive rod is provided as standard. Units are shipped with the drive rod inserted in the drive blade. Drive rod may 

be extended up to 8" beyond the outside edge of the frame by loosening the U-bolt, drawing out the rod to the desired length and then 

retightening the U-bolt. 

• 

If required, 24" and 36" long zinc-plated steel drive rods can be ordered.

•  Before installing, inspect the AIR-IQ2 Unit for possible damage caused in shipping. 
• 

If minor damage has occurred to frame corners or flanges, correct by bending them back into position gently, taking care not to disturb the 

EBTRON sensor probes and transmitter. 

• 

Do not install the AIR-IQ2 Unit if damage is more than superficial, if uncertain as to extent of damage, or if the damper does not seal correctly. 

Call TAMCO customer service at 1-800-561-3449. 

• 

Operate the damper section manually (on a flat section of floor) to verify correct blade action and sealing. 

1. 

To correctly verify sealing action, loosen the hex nuts of the U-bolt located on drive blade. Extend the steel drive rod to maximum of 8" 

beyond the outside edge of the frame. Re-tighten the hex nuts on U-bolt. 

2. 

Using the drive rod, slowly apply closing torque, while ensuring that the damper frame does not twist due to torque being applied. (Larger 

units may require an additional person to hold the damper frame square and true.) 

3. 

If possible, use daylight or an inside light source as a backdrop to the verification procedure. No light should be visible through the damper. 

CAUTION SHOULD BE EXERCISED TO ENSURE FINGERS ARE NOT IN THE WAY OF MOVING LINKAGE PARTS OR BLADES.

VERIFY BEFORE INSTALLATION!

FRONT / TOP END UP / RIGHT HAND

(viewed from damper side)

WARNING: 

 

DO NOT ADJUST DAMPER LINKAGE 

MECHANISM. TAMPERING WITH 

LINKAGE WILL VOID DAMPER 

WARRANTY. IF PROBLEM STILL 

EXISTS AFTER COMPLETING PRE-

INSTALLATION VERIFICATION, 

CALL TAMCO CUSTOMER SERVICE. 

4

TAMCO’s all aluminum dampers are constructed with maintenance-free bearing and linkage components.

CAUTION: NEVER USE ANY LUBRICANTS, SUCH AS GREASE OR SILICONE ON TAMCO DAMPERS. 

 

In applications where the humidity level is unusually elevated, or where there are extremely high levels of dust and dirt 

particles, TAMCO recommends that the damper linkage and bearing system should be cleaned once a year. This can be 

done easily with the use of a domestic strength steam cleaner. The loosened dirt and water droplets can then be blown 

out with compressed air.

CAUTION:

 

TO PREVENT DAMAGE TO EBTRON SENSORS OR TRANSMITTER, NEVER APPLY STEAM, CLEANSER OR 

COMPRESSED AIR TO THEM.

CAUTION: DO NOT USE PROBES AS HANDLES TO LIFT AND/OR POSITION DAMPER. DAMAGE TO THE PROBES MAY OCCUR.

  

Summary of Contents for AIR-IQ2

Page 1: ...STALL GUIDE_2022_04 INSTALLATION GUIDELINES T A Morrison Co Inc P O Box 157 Smiths Falls Stn Main Ontario Canada K7A 4T1 800 561 3449 Fax 800 668 8476 tamcodampers com EBTRON Inc 1663 Hwy 701 S Loris SC USA 29569 800 2EBTRON 232 8766 Fax 843 756 1838 www ebtron com ...

Page 2: ...rt Up Guide under separate cover Available individually or as a part of EBTRON A4 EF O M Manual LIMITED PRODUCT WARRANTY DESCRIPTION AIR IQ2 products are warranted against defects in materials or workmanship for 36 months from the date of shipment Should the product or component parts qualify as a warrantable failure within this time period the product or component involved will be repaired or rep...

Page 3: ...ions or issues not covered in this document contact TAMCO Customer Service at 1 800 561 3449 EBTRON AIRFLOW MEASUREMENT STATION Refer to the EBTRON A4 EF2 O M Manual under separate cover for airflow measurement station wiring instrument setup and operation For additional assistance with EBTRON Airflow Measurement Station questions or issues not covered in the O M Manual contact your local EBTRON R...

Page 4: ... back into position gently taking care not to disturb the EBTRON sensor probes and transmitter Do not install the AIR IQ2 Unit if damage is more than superficial if uncertain as to extent of damage or if the damper does not seal correctly Call TAMCO customer service at 1 800 561 3449 Operate the damper section manually on a flat section of floor to verify correct blade action and sealing 1 To corr...

Page 5: ... is not connected to the leading end of the assembly If AIR IQ2 unit is manufactured as Sleeve Only without the 1 flare the unit may be flanged to the duct so that the minimum distance from the outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10 AIR IQ2 unit must be installed square A Flanged to Duct Install Type AIR IQ2 unit damper s finished inside frame dimen...

Page 6: ...l always be on the face of damper downstream from the louver and will ship with all damper units that are two sections wide Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information AIR IQ2 shown with sleeve and flare INSIDE ...

Page 7: ...carried out by affixing only the damper inside the duct work Do not use sleeve or flare to secure unit in duct work AIR IQ2 unit must be installed square An Installed In Duct Install Type AIR IQ2 unit damper s finished outside frame dimensions are smaller than the specified duct width and height dimensions to allow for clearance to insert the damper frame into the duct work Ensure that the duct is...

Page 8: ...Non ducted applica on 4 5 6 5 1 2 4 12 5 Ducted applica on 13 5 Minimum distance to trailing edge of intake louver 9 B B 0 5 1 A 0 5 A 2 5 A 1 4 Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information Jumpers will always be...

Reviews: