OPERATION AND FUNCTION

ADJUSTMENT VOLUME

ADJUSTMENT BOX

Flashing is useful to threaten and notice incendiarism.



 

Delay time (Operation time adjustment)

Day light (Operation mode)

(1) Operation

(2) Mode Setting

Detection Function

Output function

Detection timer 

1 2

OFF

OFF

1 2

OFF

ON

1 2

ON

OFF

1 2

ON

ON

The following 4 levels are selectable.

ADJUSTING BOX DETECTION TIME

PURPOSE/EXAMPLE

DETECTION TIMER

(outputs when 

fl

ames for 

more than the below time)

Flashing

1 sec.

6 secs.

15 secs.

30 secs.

Sensitivity 

Flame of lighter/match detection at 
non-smoking areas. [Factory set]

In case of uncertain operation on 
the above two.

Fire detection

Fire detection in uncertain 
environment.

3

H

3

L

ADJUSTING BOX

SENSITIVITY

SENSITIVITY

H : 100%
      [Factory set]

L : 50%

OUTPUT CONDITIONS

(circumference brightness)

ADJUSTING VOLUME

DAY LIGHT

Output only night time

Output both day/night time
[Factory set]

5

(S)

(short)

(long)

(L)

5

(5 sec.)

(10 min.)

(2 sec.)

(1 min.)

ADJUSTING BOX

DELAY TIME RANGE

OPERATION TIME

(adjustment limit)

ADJUSTING VOLUME

DELAY TIME

approx. 2 secs.
      ~approx. 1 min.
  Factory set
  : approx. 2 secs.

approx. 5 secs.

     ~approx. 10 mins.

4

ON

NIGHT

NIGHT

& DAY

4

OFF

ADJUSTING BOX

FLASHING

OUTPUT TYPE

Continuous output
[Factory set]

Repetition of 

fl

ashing

(0.5 sec. output, 0.3 sec. stop)

[

[

The following two output types are selectable.

The operation LED (red) will light and start output when the 
sensor detects flame (ultraviolet ray) for the set up time (1 sec., 
6 secs., 15 secs., 30 secs.,) and moreover  when  the  environment 
is darker than the [operation mode] set up.
In case it still keeps flaming, it will confinue the above operation 
LED (red) lighting and output. After the flame goes out, the 
operation LED (red) lighting and output (off delay) will stop 
according to the [delay time range] (2 secs. 

10mins.). 

The following settings and functions are selectable for detection 
and output. 
Use the dip switch in the adjustment box and adjustment 
volume which is on the bottom of the sensor.

The adjustment volume can be turned by coins. 

   Do not turn strongly, it may cause damage.

This product detects ultraviolet ray included in flames and 
outputs an alarm. Outdoor installation would cause much more 
false detection than indoor installation, as there are many other 
ultraviolet ray factors and few shielding objects. 
The 8 selectable sensitivity levels combined by 2 sensitivity set 
ups and 4 detection timer set ups  are made to prevent false 
detection in such uncertain conditions outdoors. Select the set 
up that suits most the environment and purpose.
When the sensor does not operate properly, set the sensitivity to 
"L" and detection timer to the next longer time.

This function sets up the minimal flaming time to detect. 
It outputs an alarm when the flaming continues more than the set 
up time. It will not output an alarm when the flame goes out 
before the set up time.

The detection distance for "L" is half

 

of that for "H", when 

detecting same flame.
When there is uncertain operation at "H", change the sensitiv-
ity to "L".

 

For outdoor use, "L" is recommended.

The alarm may delay when the strength of ultraviolet ray is low.
Intermittent ultraviolet ray will not be detected.
Timer set up with 6 secs. or more is recommended for outdoor installation.

This function set up the size of flame (the 
strength of ultraviolet ray) to detect.

For subtle set up, adjust the volume when the circumference 
is at the requested light level.
Even setting up for night time mode, it may not output a signal 
when the circumference is bright with lightings etc. In that 
case, turn the volume to right until it outputs a signal.
The "output only night time" function is convenient to detect 
only at night time in the locations that have other ultraviolet 
ray factors at day time.
Please set "off" in "Alarm memory function" when setting up 
this function.

The following output will be produced only when the circum-
ference is darker than the set up. (day / night time discernment 
function) Set up according to purpose.

The output time for day time is off delay of detection time + set 
up time. There are following selections.

Summary of Contents for FS-5000E

Page 1: ...nnect equipment that exceeds the indicated output capacity It may cause fire We appreciate your purchase of a TAKEX flame sensor This sensor will provide long and dependable service when properly inst...

Page 2: ...the unit from falling and to maintain resistance to rain A high installation location is recommended to prevent vandal ism over 2 5m This product is for installation on walls ceilings and under eaves...

Page 3: ...AME OF N HEPTANE 23 62 60cm 66 20 m 49 15 m 33 10 m 16 5 5 m 16 5 5 m 33 10 m 49 15 m 66 20 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5 m 33 10 m 49 15 m 66 20 m 83 25 m 100 30 m 16 5 5...

Page 4: ...emporary and confirm the area and operation Make a hole through the 4 mounting holes knock outs by a driver etc Fix the mounting box by the 4 6 30 tapping screws to the surface Fix the mounting base t...

Page 5: ...om of the sensor The adjustment volume can be turned by coins Do not turn strongly it may cause damage This product detects ultraviolet ray included in flames and outputs an alarm Outdoor installation...

Page 6: ...power on reset operation Set up for area check Factory set Indicates Factory set Manual reset Power supply off and on again or Alarm memory function off This function monitors the strength of nuisance...

Page 7: ...week Do not fail to check operation whenever furniture in the vicinity is moved When the battery is low change it for a new one immediately If the battery is not changed the sensor may not operate OP...

Page 8: ...product repairs made after our Warranty Period has expired No 04 990 1406 In Japan Takex America Inc 4 15 Howleys Road Notting Hill VIC 3168 Tel 61 03 9544 2477 Fax 61 03 9543 2342 Takenaka Engineerin...

Reviews: