 Prepare the maintenance cover.

(1) 

Attach the maintenance cover fixing bracket 

      to the maintenance cover.

 (

flat washer M4 x 10, cap washer, cap cover

When attaching the maintenance cover fixing bracket, 

fix it at the bottom edge of the oval hole of the maintenance 

cover.

Cap cover

Cap washer

Flat screw

Maintenance cover

fixing bracket

(1) 

Referring to the “Attachment position of the floor fixing bracket”, temporarily place the floor fixing bracket on the 

      floor. The temporarily placed position of the floor fixing bracket should be based on the base center and the base 

      edge.

(2) 

Fix the floor fixing bracket with screws.

      If in case of a mortar floor, use anchor bolts.

   (5 x 30 tapping screw, 2 pcs.)

Ŷ,QVWDOODWLRQPHWKRGRIDERYHWKHIORRUSOXPELQJ

(3) 

Install the water, hot water supply pipe, and drain pipe on floor.

  Refer to the “Plumbing layout” for the installation position.

After temporarily placing the floor fixing bracket on the floor, be sure to attach the plumbing 
cover C and the maintenance cover (cut), and check and confirm the fixing position.

C A U T I O N

 

*If in case you will cut the length of the plumbing cover C

, the number of the floor fixing 

 bracket used would change accordingly.

(4) 

Joint the drain pipe and the raised drain pipe as shown in the 

      right illustration. Be sure to insert the drain hose packing to

      the raised drain pipe thoroughly.

  

(5) 

Attach blade flexible pipe and stop valve as shown 

       in the right illustration.

* The knob of the water stop valve should be facing opposite 

  side of the chair unit.

Drain hose packing (attached to main unit)

Drain hose fixing clamp (attached to main unit)

Drain hose

Raised drain pipe

[Hot water]

[Water]

Filtered check valve

Flexible pipe (accessory of 

the RS

basin unit)

Packing (accessory of 

above the floor plumbing kit)

Stop valve (with single nut, accessory 

of above the floor plumbing kit)

Packing (accessory of above 

the floor plumbing kit) 

Check and confirm if there is no bend or damage on the drain hose. Failure to follow 

  this instruction may cause bad flow of drain or breakage of the drain hose.

Make sure if the drain hose clamp is attached firmly. If it is not attached firmly, 

  this may cause water leakage and drain hose may come loose.

C A U T I O N

 

(6) 

After the plumbing work is finished, refer to “2. Piping 

      (3. Test water flow, Cleaning)” of the “RS

 Installation Instructions”.

(7) 

Cut the plumbing cover C based on the installation position of the basin unit.

Floor fixing bracket

Floor fixing bracket

* The black caps are provided for covering the screw heads.

Follow to the instructions shown in the "How to adjust faulty temperature 

regulation (Page 10)" shown in the "RSIII Installation Instructions".
* When attaching the reducing valve, make sure that the position 
   of filter should be higher than original position. The plumbing cover 
   prevents stop valve from opening and closing smoothly.

* To attach reducing valve smoothly, remove the front cover to 

  detach the flexible pipe between thermostat and filter.

* Be sure to do this process. Failure to follow this instruction may cause water leakage inside of the plumbing cover leading to corrosion of the 
  plumbing cover and floor.

* The screw holes of the plumbing cover C are oval holes to allow minor adjustment 
   of the fixing position.
* The screw holes of the floor fixing brackets are made larger than the fixing screws 
   to allow minor adjustment of the fixing position.

(11) 

Install the maintenance cover (cut) referring to “4. Attach cover (2. Mounting the Maintenance Cover (Page 16))” of

        the “RS III  Installation Instructions”.

     

 Then, continue the installation after the process “After installation (Page 24, 25)”

.

(8) 

Place the plumbing cover C over the floor fixing bracket, and check the below points.

 1. Check and make sure that there is no large clarance at the jointed parts of the plumbing cover C.

     2. Check and make sure that the plumbing cover C could be fixed correctly to the floor fixing bracket with screws.

(9) 

After checking the installation work, fix the plumbing cover C with screws.

     

SFVRI0[VFUHZVDQGSFVRIZDVKHUijSHURQHIORRUIL[LQJEUDFNHW

   

 After screwing is finished, cover the screw head with the black caps provided with the screws.

(10) 

Apply caulking materials to any gaps between the plumbing cover C and floor.

1E01K4A0

7.2

 

Hole 

Depth 

30

(1) Drill open a hole of the 

     specified diameter and 

     depth.

(2) Remove the dust from each 

     anchor hole by cleaning with 

     a vacuum cleaner.

ĺ

 

(4) 

Attach the floor fixing bracket

     and fasten the tapping screw

     using a screwdriver.

(3) 

Insert the anchor bolt lightly 

     in the hole.

Installing screws (In the case of fixing the floor fixing bracket to mortar floor.)

Floor fixing bracket

 

Floor

     If in case the plumbing cover C can not be fixed correctly, check and correct the “Attachment position of the floor 
     fixing bracket”.

Reducing valve

(Sold separately

Filtered check

valve

Front 

cover

Stop valve

How to adjust faulty temperature regulation