MAINTENANCE
MAINTENANCE
On-Demand Water Heater Service Handbook for 240, 340 & 540 Condensing Models • 67
8. Reconnect the drain pipe (item
465) as shown in the diagram on
Secure both ends with 6-15 clips.
9. Slide the burner into the combustion
chamber. (See Figure 66.) There
are grooves on the sides of the
combustion chamber; the top and
bottom of the burner has flanges and
spacers that will will slide along the
grooves.
NOTICE: Install with caution. The
flanges along the bottom of the
burner are rigid, but the spacers
along the top of the burner are
fragile and can be damaged easily.
Ensure that the flanges /spacers
are in alignment with the grooves
before sliding the burner into
place.
9.3.1
Insert and hand tighten two
(2) screws below the burner,
will secure the burner to the
back of the cabinet. You may
need to push the assembly
up some in order to line up
the holes.
9.3.2
Insert and hand tighten
three (3) screws along the
top, front portion of the
10. Insert the outlet tubing into the
water outlet connection, making
sure that the brass ring on the
tube goes all the way in and is
flush with the top of the outlet
connection (Figure 67).
Secure it with a 16-25 clip. See
11.
Attach the top of the condensate
drain tube to the port on the bottom
of the secondary heat exchanger. (See
12. Install the fan with the air inlet
facing toward the front as follows:
12.1
Slide the fan’s flanges into
the slots on the bottom of
the combustion chamber.
(The fan’s air inlet must face
outward.)
12.2 Line up the holes, then insert
and hand-tighten two (2) hex
head screws with washers
NOTICE:
There are two
holes on the bottom of the
case through which you can
reach both screws with an
8-inch long phillips screw
driver (#2).
13. Install the gas valve/manifold
assembly as described below.
(See also item 102, p. 73)
13.1
Attach a wire connector to
each of the solenoid valves
as described:
•
There are a total of five
connectors to be reinstalled.
•
Each connector has a dark
blue wire, except for the
proportional valve. The
other wire colors will vary.
•
Each set of wires has a tag
with a number on it, and
each solenoid valve has a
number stamped next to
it. During installation, each
wire number must match
its solenoid valve number.
•
Install each connector to
Example:
Hot Outlet Tube Installation
Once tube is installed,
secure with fastener 16-25.
Bottom, left-hand side of case
Figure 67.
Solenoid
(locations vary)
Connector
Numbered
Wire
Stamped
Number
In each case, these numbers
must match.
Connectors have no polarity.
Figure 68.