TCAC-RTSM-20150203 Tadiran Domestic Pool Type Technical Manual
2.7 Installation
2.7.1 Transport
Choose the correct way of conveying the equipment.
Try to transport the equipment with the original package.
The main unit should be put down gently during transportation, and main unit should not be
leaned more than 45 degree.
Guard boards should be applied to avoid scratching and deforming of the unit surface.
2.7.2 Main unit installation
Location of outdoor installation
After move onto installing site, please confirm the main unit is placed in horizontal.
Do not install the heat pump close to inflammable gas source.
Do not install the heat pump close to a road or path to protect the appliance against mud
splashing.
Avoid places that are subject to strong winds, in particular if the wind blows against the
appliance’s air outlet.
Ensure enough space for installation and maintenance.
A distance of no less than 200mm should be preserved between the bottom of the outdoor
unit and the ground or bracket for the installation of the duct pipe.
If the unit installed in an underground chamber, an indoor room or other hermetic place, pay
attention to where surrounding air, as well as which air exhaust and air circulating system.
For every signal unit, which circulating air volume shall no less than 2400m
3
/h.