12.2.11 TECHNICAL MENU (MAX PRO MOD.)
Proceed as follows to access the technical menu:
1)
Press the
UP
and
DOWN
buttons simultaneously for
5 s
, the message
“tECH”
will appear in the display.
2)
Press the
“SET”
button and select the parameter to be displayed by pressing the
UP
or
DOWN
buttons
(see TAB. 23).
3)
Press the
“SET”
button to select the desired parameter.
INFORMATION
AFTER
10 S
OF INACTIVITY, THE CIRCULATOR LEAVES THE TECHNICAL MENU AND RETURNS TO NORMAL OPERATION.
FIG. 14 (Technical menu)
Parameters
Meaning
T 0
Display Firmware version
T 1
Inverter Firmware version
T 2
Unit of measurement shown on the display:
• SI = Système international (European)
• IU = Imperial units (Anglo-Saxon)
T 3
Maximum pump head / model (60-80 or 100)
T 4
Analog input voltage 0-10 V
T 5
"Duty cycle" PWM input
T 6
Mains voltage
T 7
Internal inverter voltage
T 8
Pump working hours (in thousands, 0.010 = 10 hours, 101.0 = 101000 hours)
T 9
Ignitions counter
T 10
Standby counter
T 11
Rotor blocks counter
T 12
Step losses counter
T 13
Undervoltages counter
T 14
Overvoltages counter
T 15
Counter for missing internal cards communications
TAB. 23 (Technical menu parameters)