3. - Settings
The necessary basic settings required for
the control function are made in menu “5.
Settings”.
Caution
This does not under any circumstances
replace the safety facilities to be
provided by the customer!
The menu is closed by pressing “esc” or
selecting “Exit settings”.
Settings
Attention
3.1. - VFS Type
This menu is used to set the type of VFS sensor used.
VFS-Type- Settings range: 5-100, 10-200, 20-400 l/min / Default: 20-400 l/min
3.2. - Threshold 1
This menu is used to set the fl ow rate, at which the relay is being switched.
Settings range:
Switch-on value: 1 to 400 l/min / Default: 30 l/min
Switch-off value: 1 to 400 l/min / Default: 20 l/min
The FWCK can control the fl ow to 4 more fresh water stations by means of stop valves.
The fi rst fresh water station runs independently. The secondary fresh water stations
fl own are controlled via stop valves. A fl ow sensor is integrated into every single
station. The FWCK is monitoring the entire fl ow. 4 On and Off limits are set in the
FWCK, at which the individual stations stop valves are switched.
To ensure an equal use of the fresh water stations the FWCK changes the station
switched fi rst when the fl ow reaches 0 L/min.
To deactivate stations 2 to 4, the switch-on value can be set to „Off“.
Every Fresh water station has to be equipped with a fl ow limiter to prevent
damage to the VFS sensor.