KOM03 TOTAL
FAULT MES-
SAGE
Option: Fault
message
output
Here, the fault messages and info
messages are also diverted to the
output.
n
-1: No voltage is output if there
is a total fault message pending.
n
0: This function is not used.
n
1: Voltage is output if there is a
total fault message pending.
-1;0;1
0
25
08:111
KOM04 EBUS
ADDRESS
eBUS address
Addressing of the controller in the
eBUS network
2...16
-
25
04:020
KOM05 EBUS
SUPPLY
Voltage supply for eBUS communi-
cation, max. load 180 mA.
on/off
-
25
04:036
STE
CONTROLS
STE11 TPV SENSOR
TYPE
TPV PWT pri-
mary flow
sensor selec-
tion, sensor
type
n
0: NTC 5K
n
1: PT 1000
0...1
-
25
28:027
STE12 MIN.RUN-
TIME TPV
PROTEC
Min. runtime
for primary
pump cycle/
protective
function
Is active if the temperature at TPV
falls below the value TPVset. This
serves to protect the heat source
from cooling down too signifi-
cantly. The value specifies the
minimum runtime/test time in
which the temperature is not per-
mitted to drop.
0...180
s
25
36:025
STE13 MIN.OFF-
TIME TPV
PROTEC
Waiting time
for the primary
pump cycle/
protective
function
Is active because TPV has fallen
below the value TPVset after the
minimum runtime; the pump
remains blocked for the setting.
This allows the heat source to
increase the temperature again.
0...60
min
25
36:026
MAN
MANUAL
Adjuster only has an effect if the
operating mode selection is “Manual"
.
MAN01 SPEED PRIM.
PUMP
Manual value
output
Primary pump (FRIWA; PP)
0...100
%
0
08:088
MAN02 SPEED CIRC.
PUMP
Manual value
output
Circulation pump WWC
0...100
%
0
05:122
MAN03 RETURN
FLOW
SWITCH
Manual value
output
Return flow switch valve VSR
on/off
-
0
05:120
ES 5941
Info and menu parameters
08/2020 Item no. 215790 EA no. 1321
Operating instructions
33