CONTROL UNIT MOUNTED ON PROBE

FIG. 3

LWCO

FIG. 4

1.  Be sure the probe is installed above the 

minimum safe

 water 

level, as previously determined from the boiler manufacturer’s 
literature.

2.  Be sure the probe extends into the boiler cavity or piping so that 

contact with the water is made. Do not install in locations where 
air can be trapped.

3. Be sure the exposed portion of the stainless steel probe is a 

minimum

 of 1/4” from any grounding surface inside the boiler 

to prevent the probe from shorting (see Fig 1).

INSTALLATION
IMPORTANT NOTES FOR PROBE INSTALLATION:

 

Control Unit Mounting onto Probe (See Fig. 3):

1. Tighten the probe into the tapped location of the boiler with a 

wrench, using the bushing flats provided.

2. Make sure the heads of the two mounting screws in the probe 

bushing are loosened approximately 1/8” from the bushing 
surface.

3. Then remove the first lock washer/nut from the probe threads.

4. Orient the slotted holes in the control unit over the heads of the 

mounting screws of the probe and turn control unit counter-
clockwise so that the ends of the slots are fully under the mounting 
screw heads. Tighten mounting screws.

5. Replace the probe locknut onto the electrode threads and tighten.

Only use pipe thread sealant for sealing probe threads.  Do 
not use Teflon tape.  Use of Teflon tape can insulate probe 
electrically and can cause improper device operation and 
damage to equipment or property.   

 

DWG# 3576-3

AMBER “SERVICE”

TEST BUTTON

BI-COLOR “STATUS”

GROUND SCREW

PROBE

TERMINAL BLOCK

FACTORY INSTALLED JUMPER 
(REMOVE IF LWCO POWER 
SOURCE IS DIFFERENT THAN 
BURNER POWER SOURCE)

PROBE 
LOCKNUT

DWG# 3576-2

MOUNTING 

SCREWS

DWG# 3576-4

3/4 NPT FITTING

LWCO OUTLINE DRAWING

FIG. 5

Summary of Contents for LTA-2

Page 1: ...ing NEMA 1 for indoor use only Input Power 2 8 VA 120 VAC 2 8 VA 24 VAC supplied by a Class 2 power source Reset Automatic reset when water level returns to safe level Testing Integrated test switch for testing safety shutdown US Patents 6 904 800 7 243 540 and 7 317 993 Other Patents Pending Installation must be performed by qualified personnel and in accordance with all national and local codes ...

Page 2: ...robe so that the exposed portion of the stainless steel is a minimum of 1 4 from any grounding surface inside the boiler to prevent the probe from shorting See Fig 2 4 Tighten probe securely with a wrench using bushing flats provided Use pipe thread sealant to seal the probe threads tures Status LED Service LED Test Button Do not tighten by grasping the device enclosure Use wrenching flats on the ...

Page 3: ... the two mounting screws in the probe bushing are loosened approximately 1 8 from the bushing surface 3 Then remove the first lock washer nut from the probe threads 4 Orient the slotted holes in the control unit over the heads of the mounting screws of the probe and turn control unit counter clockwisesothattheendsoftheslotsarefullyunderthemounting screw heads Tighten mounting screws 5 Replace the ...

Page 4: ...onnect wire from the hot side of the water feeder or alarm to terminal NO Be sure the power source for Control Unit and burner circuit are the same voltage Make sure you are not introducing a second voltage source into the burner circuit via the jumper This will bypass other operating limit and or safety controls which may result in property damage personal injury or death Testing 1 DO NOT fill bo...

Page 5: ...dels w Red Green LEDs H N C B W McDonnell Miller Series 750 1 2 3 4 5 McDonnell Miller RB 122 H Black Wire N White Wire C Yellow Wire B Yellow Wire McDonnell Miller RB 120 1 2 3 4 5 McDonnell Miller RB 24 Red Wire White Wire Yellow Wire Yellow Wire Hydrolevel 24 Black Wire White Wire Orange Wire Brown Wire Hydrolevel 170 H GN P1 P2 A Hydrolevel 400 500 600 700 450 550 650 750 1 2 P1 P2 A Honeywell...

Page 6: ...NTAL COSTS OF REMOVING OR REPLACING DEFECTIVE PRODUCTS This warranty gives the purchaser specific rights and the purchaser may have other rights which vary from state to state Some states do not allow limitations on how long an implied warranty lasts or on the exclusion of incidental or consequential damages so these limitations or exclusions may not apply to you Symptom Possible Cause Remedy Boil...

Reviews: