background image

6

FAULTS

CONTROL 

PANEL

CAUSES

REMEDIES

The circulator is 

noisy

LED on 

Suction pressure is 

insufficient - cavitation 

Increase the system suction 

pressure within the 

permissible range.

LED on

Presence of foreign bodies 

in the impeller

Disassemble the motor and 

clean the impeller.

Loud noises of 

water circulation

Flashing white 

LED

Air in the system. Pump

may be air-bound. 

Vent the system. Repeat 

fill and purge steps.

Circulator is not 

running although 

the electrical 

power supply is

switched on

LED off 

Lack of power supply

Verify voltage value of the 

electric plant.

Verify the connection of the 

motor.

Circuit breaker might be

tripped

Check circuit breaker at panel

and reset if necessary

The circulator is defective

Replace the pump.

Overheating

Let the pump cool down for 

some minutes. Then try to re-

start it. Verify that the water 

and ambient temperature are 

within the indicated 

temperature ranges.

LED red 

The rotor is blocked

Disassemble the motor and 

clean the impeller. See 

unlocking procedure below.

Insufficient supply voltage

Verify that the power supply 

matches the data on the name 

plate.

Building does not 

get warm.

LED on

System may be air-bound

Vent system.

Repeat fill and purge steps.

8.  Unlocking Procedure: 

A red light in the LED indicates the circulator is locked or sticking. Disconnect and connect power supply

to start the automatic release process. The circulator makes 100 attempts to restart (process lasts approximately 15 minutes).

Every restart is signalled by a short white flash of LED light. If the locking is not removed through the automatic release process

after 100 attempts to restart the circulator, it goes into standby and the LED remains red. In this case follow the manual procedure

described in the next steps: during any attempt, the red LED light keeps blinking; after that the circulator tries again to start. If

the locking is not removed through the automatic release process (the warning light returns to be red), perform the manual steps

described below.

1. Disconnect power supply - the warning light switches off

2. Close both isolating valves and allow cooling. If there are no shut-off devices, drain the system so that the fluid level is

beneath that of the circulator

3. Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor

4. Remove impurities and deposits from the impeller and casing

5. Reinsert the rotor/impeller into the motor

6. Connect power supply. Check for impeller rotation

7. If the circulator still doesn’t run it will need to be replaced

7.  Troubleshooting the error codes: 

Listed below are potential diagnostic error codes which will appear on the LED display in case

of a malfunction.

Summary of Contents for 007e-2 Series

Page 1: ...nblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these applications AVERTISSEMENT Ne pas utiliser dans une piscine ou un spa La pompe...

Page 2: ...COMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED Figure 2 ...

Page 3: ...GING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 ...

Page 4: ...D or the double insulation symbol square within a square In a double insulated appliance two systems of insulation are provided instead of grounding No grounding means is provided on a double insulated appliance nor should a means for grounding be added Servicing a double insulated appliance requires extreme care and knowledge of the system and should be done by qualified service personnel Replace...

Page 5: ... run the circulator long enough to remove all remaining air from the bearing chamber This is especially important when installing the circu lator in the off season An orange LED will illuminate when the 007e 2 is powered on 6 Green Mode Responsive technology actively monitors system condi tions and automatically adjusts to optimize power consumption CAUTION Never run the circulator dry or permanen...

Page 6: ...the LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash of LED light If the locking is not removed through the automatic release process after 100 attempts to restart the circulator it goes in...

Page 7: ...ntact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construction or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES...