VI, V2, V3 = SHUT-OFF ISOLATION VALVE
P = TACO CIRCULATOR WITH IFC
FF = FAST FILL BOILER FEED VALVE
PV4 = PURGE VALVE

RECOMMENDED PURGING STEPS:

1. CLOSE V1, PV4, V2
2. OPEN V3
3. OPEN FF VALVE
4. OPEN V2, PV4, TO PURGE LAST ZONE

  FIRST (ZONE 3)

5. CLOSE FF VALVE
6. CLOSE V2, PV4
7. REPEAT STEPS 1 TO 6 FOR EACH 

  ADDITIONAL ZONE, PURGE ZONE 1 LAST

8. OPEN V1 WHEN ALL ZONES ARE

  PURGED

9. ADJUST SYSTEM TO DESIRED OPERATING 

  FILL PRESSURE IF REQUIRED

Figure 2:

Summary of Contents for 007e-2 Series

Page 1: ...nblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these applications AVERTISSEMENT Ne pas utiliser dans une piscine ou un spa La pompe...

Page 2: ...COMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED Figure 2 ...

Page 3: ...GING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 ...

Page 4: ...D or the double insulation symbol square within a square In a double insulated appliance two systems of insulation are provided instead of grounding No grounding means is provided on a double insulated appliance nor should a means for grounding be added Servicing a double insulated appliance requires extreme care and knowledge of the system and should be done by qualified service personnel Replace...

Page 5: ... run the circulator long enough to remove all remaining air from the bearing chamber This is especially important when installing the circu lator in the off season An orange LED will illuminate when the 007e 2 is powered on 6 Green Mode Responsive technology actively monitors system condi tions and automatically adjusts to optimize power consumption CAUTION Never run the circulator dry or permanen...

Page 6: ...the LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash of LED light If the locking is not removed through the automatic release process after 100 attempts to restart the circulator it goes in...

Page 7: ...ntact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construction or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES...

Reviews: