background image

A Taco Family Company

102-517A

SUPERSEDES: New

EFFECTIVE: April 7, 2017

Plant ID No. 001-5000

007e

ECM High-Efficiency Circulator

DESCRIPTION:

The 007e-2 is a variable speed, high-efficiency wet rotor circulator with an ECM, permanent mag-

net motor. Its ECM performance is equivalent to the legendary Taco 007 and ideal for hydronic

systems zoned with circulators or zone valves. It reduces power consumption by up to 85% com-

pared to equivalent AC permanent split capacitor circulators.

APPLICATION:

     •   Maximum operating pressure: 125 psi (8.6 bar)
     •   Maximum water temperature: 230°F (110ºC)
     •   Electrical specifications:

             Voltage: 110-120V, 50/60 Hz, single phase

             Maximum operating power: 44W

             Maximum amp rating: 0.54

     •   Equipped with a cast iron casing and should be used for closed loop systems only
     •   Taco circulator pumps are for indoor use only – employer uniquement a l’interieur
     •   Acceptable for use with water or maximum of 50% water/glycol solution

FEATURES:

     •   ECM performance equivalent to the legendary Taco 007 circulator

     •   Multi-color LED display showing power on and error code diagnostics

     •   Use with a Taco Zone Valve Control (ZVC) or Switching Relay (SR) for ON/OFF operation

     •   Nut capture feature on flanges for easier fit up

     •   Dual electrical knockouts and 6” stranded wire leads for easy wiring

     •   Double insulated - no ground-wire required

     •   Whisper quiet operation

     •   BIO Barrier

®

protects the pump from system contaminants

     •   

SureStart

®

- automatic unblocking and air purging mode

     •   Optional 2-way universal flange model for easy fit-up to any flange orientation

     •   Integral Flow Check (IFC

®

) included - Field installed

     •   Green Mode active system monitoring and power optimization  

INSTALLATION:

WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.

AVERTISSEMENT: Ne pas utiliser dans une piscine ou un spa. La pompe n'a pas été étudiée pour ces applications.

CAUTION: The addition of petroleum based fluids or certain chemical additives to systems using TACO equipment voids the war-

ranty. Consult factory for fluid compatibility.

ATTENTION: L'ajout de liquides à base de pétrole ou de certains additifs chimiques à des systèmes utilisant un équipement TACO

annule la garantie. Consultez le fabricant pour connaître la compatibilité de liquides.

CAUTION: Installations at elevations over 5000 feet must have higher fill pressure of 20 psi minimum to prevent pump cavitation

and flashing. Premature failure may result. Adjust expansion tank pressure to equal fill pressure. A larger size expansion tank may

be required.

ATTENTION: Des installations à des altitudes de plus de 1600 mètres doivent présenter une pression de remplissage plus élevée

de 20 psi au minimum afin d'éviter toute cavitation ou flashing de la pompe. Une défaillance prématurée peut en résulter. Réglez

la pression du réservoir d'expansion de façon qu'elle soit égale à la pression de remplissage. Un réservoir d'expansion d'une taille

supérieure peut être nécessaire.

Instruction Sheet

®

Standard flange model: 007e-2F2

Optional 2-way flange model: 007e-2F4

Figure 1:

Summary of Contents for 007e-2 Series

Page 1: ...nblocking and air purging mode Optional 2 way universal flange model for easy fit up to any flange orientation Integral Flow Check IFC included Field installed Green Mode active system monitoring and power optimization INSTALLATION WARNING Do not use in swimming pool or spa areas Pump has not been investigated for these applications AVERTISSEMENT Ne pas utiliser dans une piscine ou un spa La pompe...

Page 2: ...COMMENDED PURGING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED Figure 2 ...

Page 3: ...GING STEPS 1 CLOSE V1 PV4 V2 2 OPEN V3 AND ZV3 3 OPEN FF VALVE 4 OPEN V2 PV4 TO PURGE LAST ZONE FIRST ZONE 3 5 CLOSE FF VALVE 6 CLOSE V2 PV4 7 REPEAT STEPS 1 TO 6 FOR EACH ADDITIONAL ZONE PURGE ZONE 1 LAST 8 OPEN V1 WHEN ALL ZONES ARE PURGED 9 ADJUST SYSTEM TO DESIRED OPERATING FILL PRESSURE IF REQUIRED 10 MOVE ALL ZV TO CLOSED AUTOMATIC POSITION Figure 3 ...

Page 4: ...D or the double insulation symbol square within a square In a double insulated appliance two systems of insulation are provided instead of grounding No grounding means is provided on a double insulated appliance nor should a means for grounding be added Servicing a double insulated appliance requires extreme care and knowledge of the system and should be done by qualified service personnel Replace...

Page 5: ... run the circulator long enough to remove all remaining air from the bearing chamber This is especially important when installing the circu lator in the off season An orange LED will illuminate when the 007e 2 is powered on 6 Green Mode Responsive technology actively monitors system condi tions and automatically adjusts to optimize power consumption CAUTION Never run the circulator dry or permanen...

Page 6: ...the LED indicates the circulator is locked or sticking Disconnect and connect power supply to start the automatic release process The circulator makes 100 attempts to restart process lasts approximately 15 minutes Every restart is signalled by a short white flash of LED light If the locking is not removed through the automatic release process after 100 attempts to restart the circulator it goes in...

Page 7: ...ntact Taco at 401 942 8000 Taco reserves the right to provide replacement products and parts which are substantially similar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construction or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES...