Specifications:

Terminals 1 & 2:

Thermostat – 24VAC SPDT 2 wire heating thermostat, or Di-

gital Electronic 2 wire 24VAC thermostat with a maximum

current draw of 30 milliamps.

Anticipator Setting – 0.20.

Cycles –Too frequent, adjust upward. Too long, adjust down-

ward.

Terminals 3 & 4:

Relay – Dry Contact Switch Ratings

• 240VAC 1 Phase 5 Amps

• 115VAC 1 Phase 5 Amps

• 24VAC 1 Phase 5 Amps

Testing Sequence:

1. Restore Electrical Power.

2. Turn room thermostat ‘ON’.

3. Circulator will start:

• Green LED light turns ‘ON’

• Relay-contact will close between terminals 3 & 4

Testing Priority Switch:

1. Turn Priority Circulator room thermostat ‘ON’.

2. Priority Circulator Starts:

• Green LED light turns ‘ON’

• Relay-contact will close between terminals 3 & 4

• All Non-Priority circulators will turn ‘OFF’.

3. Priority Circulator room thermostat turns ‘OFF’.

• Priority Circulator stops.

• Any Non-Priority Circulators will now begin to operate.

BASIC PRIORITY ZONING CIRCULATOR WIRING DIAGRAM