Taco Comfort Solutions FuelMizer SR501-OR-4 Instruction Sheet Download Page 3

•   The sensor should be mounted on a wall which best represents

the heat load on the building (i.e. a northern wall for most build-

ings and a southern facing wall for buildings with large south fac-

ing glass areas). The sensor should not be installed near heat

sources such as ventilation or window openings.

•   The sensor should be installed at an elevation above the ground

that will prevent accidental damage or tampering.

•   Install the Outdoor Sensor and run the wiring back to the control

mounting location. 

Installing the Boiler Sensor: 

Note:

This sensor is designed to mount on a pipe or in a temperature

immersion well.

•   The sensor can be strapped directly to the pipe using the cable

tie provided. Insulation should be placed around the sensor to

reduce the effect of air currents on the sensor measurement.

•   The Boiler Sensor should be placed downstream of a pump or

after  an  elbow  or  similar  fitting.  This  is  especially  important  if

large diameter pipes are used because the thermal stratification

within the pipe can result in erroneous sensor readings. Proper

sensor location requires that the fluid is thoroughly mixed within

the pipe before it reaches the sensor. 

Step Three:

Wiring to the Zone Control: 

Line Voltage Connections –

Connect 120VAC incoming line voltage; Hot to the H terminal and

Neutral to the N terminal.
Connect 120VAC circulator; HOT lead of circulator to Zone H ter-

minal and Neutral lead of circulator to Zone N terminal.

Low Voltage Connections –

Connect thermostat or zone control end switch to the R and W

thermostat terminals.
Connect the DHW aquastat to the R and W DHW override terminals

(optional).
Connect boiler’s T and T terminal to the X and X boiler end switch

terminals.

Wiring the Sensors:  

Do not apply power to these terminals as this will damage the
control.

Outdoor Sensor 

Connect the two wires from the Outdoor Sensor to the Outdoor

Sensor terminals. The Outdoor Sensor measures the outdoor air

temperature. 

Boiler Sensor 

Connect  the  two  wires  from  the  Boiler  Sensor  to  the  Supply

Sensor terminals and insulate. The Boiler Sensor measures the

supply water temperature going from the boiler to the system.

SETTINGS:

Before adjusting the settings, read through the sequence of operation

to ensure that you understand how the control operates. The following

page describes how to program these settings into the control once it

has been powered up.

Step Four:

Outdoor Design Temperature:
The Outdoor Design setting is the outdoor tem-

perature used in the heat loss calculation. It is

set to the typical coldest outdoor temperature.

Using a small screwdriver adjust the reset ratio

knob  to  appropriate  Outdoor  Design

Temperature. When set to OFF, the boiler tem-

perature will not be reset and boiler will fire to

high limit when there is a call for heat.
Boiler Minimum Supply Temperature (Dip Switch #1):
Most boilers require a minimum operating temperature to prevent cor-

rosion  from  flue  gas  condensation.  The  minimum  boiler  dip  switch

should be set to ON (140°F) supply water temperature so boiler can

operate without causing the boiler flue gases to condense. Consult

the  boiler  manufacturer  for  recommended  minimum  boiler  supply

temperatures. The dip switch can also be set to OFF (70°F) when

condensation is not a concern.
Differential (Dip Switch #2):
The differential adjustment sets how far the actual boiler supply water

temperature may deviate from the desired temperature before the boil-

er is turned on or off. This is a function of the water content of the boiler

and the flow rate through the system pump relative to the heat output

of the boiler. The differential can be set by dip switch #2,  set to OFF for

10°F (6°C) or set to ON for 20°F (12°C). 
Pump Operation (Dip Switch #3):
The  pump  operation  is  controlled  by  dip  switch  #3.    When  the  dip

switch is set to ON, the pump output will energize when thermostat or

DHW calls for heat. When set to OFF, the pump will only come on

when the thermostat calls for heat not the DHW.
Warm Weather Shut Down: 
When the outdoor temperature rises above 70°F (21°C), the control

turns off the boiler and blinks the Thermostat LED light. This function

only applies for space heating and does not affect DHW operation.

TROUBLESHOOTING:
Step Five:

As in any troubleshooting procedure, it is important to isolate a prob-

lem as much as possible before proceeding. The blinking error LED

light greatly simplifies troubleshooting of the SR501-OR. If you sus-

pect a wiring fault, return to step three and carefully check all external

wiring and wiring connections. 
Sensor Errors:

•   If an outdoor sensor fault occurs, the SR501-OR will assume a

fixed  outdoor  temperature  of  32°F  (0°C)  and  will  target  the

appropriate supply water temperature. The Boiler light will blink

twice every 5 seconds to indicate the outdoor sensor error. 

•   If a boiler sensor fault occurs, the SR501-OR turns the boiler off

and the Boiler light will blink once every 5 seconds to indicate the

boiler supply sensor error. 

Adjustment of Settings: 

•   If  the  outdoor  temperature  is  cold  and  the  rooms  are  cold,

increase the Outdoor Design setting by 5°F (3°C) per day. 

•   If the boiler is cycling too often, increase the Differential setting.

Testing the Sensors:
A good quality test meter capable of measuring up to 5,000 k

Ω

(1 k =

1000 

Ω

) is required to measure the sensor resistance. In addition to

this,  the  actual  temperature  must  be  measured  with  either  a  good

quality digital thermometer, or, if a thermometer is not available, a sec-

Do not apply voltage to a sensor at any time
as damage to the sensor may result.

Note: When the outdoor temperature rises above 70°F (21°C), the
control turns off the boiler and blinks the Thermostat LED light.
DHW will still operate.

OFF

-30

-20

-10

0

10

20

30

40

Summary of Contents for FuelMizer SR501-OR-4

Page 1: ...to the building The SR501 OR boiler reset control utilizes a reset ratio to set the relationship between outdoor tem perature and supply water temperature The reset ratio determines the amount the supply water temperature is raised for every 1 drop in out door air temperature and it is determined from the starting point and the system design conditions In order for the control to automatically det...

Page 2: ...er Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water...

Page 3: ... limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent cor rosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boile...

Page 4: ...d and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistanc...

Reviews: