Boiler Operation:

The  supply  water  temperature  from  a  boiler  can  be  controlled  by

cycling the boiler on and off. Modulation of the boiler’s operating tem-

perature in hot water heating systems not only provides more comfort

but also offers significant energy savings. The cooler the boiler runs,

the more efficient it is due to less heat losses up the flue and reduced

boiler jacket losses. 
Differential:
An on / off boiler must be operated with a differential in order to pre-

vent short cycling. When the supply water temperature drops below

the bottom rail of the differential, the boiler is turned on. The boiler is

then kept on until the supply water temperature rises above the top

rail of the differential. If the differential is too wide, there can be large

supply  water  temperature  swings;  however,  if  the  differential  is  too

narrow, the boiler short cycles and operates inefficiently. This control

can  be  set  for  two  different  boiler  differentials,  10°F  (6°C)  or  20°F

(12°C).  This  setting  will  help  to  achieve  an  appropriate  balance

between temperature swings and boiler efficiency. 
Minimum Boiler Supply:
Most boilers require a minimum supply water temperature in order to

prevent  corrosion  from  flue  gas  condensation.  The  control  should

therefore only modulate the boiler supply water temperature down to

the boiler manufacturer’s minimum recommended operating temper-

ature. Some boilers are designed to condense and should be operat-

ed at low water temperatures as much as possible for maximum effi-

ciency.

S

U

P

P

L

Y

 W

A

T

E

R

 T

E

M

P

E

R

A

T

U

R

E

TIME

Differential = 10

°F (5 °C)

165

°F(74 °C)

155°F (68 °C)

160°F (7 1°C)

BOILER ON

BOILER ON

BOILER OFF

BOILER OFF

OUTDOOR AIR TEMPERATURE

50

(10)

30

(-1)

10

(-12)

-10

(-23)

70

(21)

90

(32)

WWSD

TEMPERATURE

°

F (

°

C)

SU

PP

LY

 W

AT

ER

 T

EM

PE

RA

TU

RE

110 (43)

70 (21)

90 (32)

210 (99)

170 (77)

150 (65)

130 (54)

190 (88)

RESET

RATIO

BOILER

MINIMUM

SEQUENCE OF OPERATION:
Powering Up the Control:

After the SR501-OR is powered up, the green power LED light will be on.

Heating Demand:

The SR501-OR receives a heating demand from thermostat or zone

control end switch closure on the R and W thermostat terminals. The

thermostat red LED light will also be turned on. The control can be

setup for boiler temperature reset or ON – OFF boiler operation.

Reset Demand:

When the SR501-OR receives a heating demand the controls enable

the boiler based on the reset curve. The Boiler Relay red LED light

will be turned on when the boiler relay is energized.

DHW Demand:

When the SR501-OR receives a DHW demand the controls enable

the boiler and ignore the boiler reset curve.  The DHW Override red

LED light will also be turned on.

Warm Weather Shut Down (WWSD):

When the outdoor temperature rises above 70°F (21°C), the control

turns off the boiler and blinks the Thermostat LED light. This function

only applies for space heating and does not affect DHW operation.

Boiler Operation:

When the SR501-OR has a reset demand, the system supply water

temperature is controlled by turning the boiler on and off. The control

calculates the target supply water temperature based on the outdoor

temperature, and the settings that were entered. The boiler operates

around a differential that is manually set by dip switch number 2. The

control includes a minimum on and off time for the boiler, in order to

minimize short cycling. 
Maximum Boiler Supply: 
The  SR501-OR  does  not  allow  the  boiler  target  temperature  to

exceed the boiler design temperature setting plus 10°F (6°C) up to a

maximum of 225°F (107°C). 
Minimum Boiler Supply: 
The SR501-OR has a 140°F minimum boiler setting which is used in

order to prevent corrosion from flue gas condensation. During mild

outdoor conditions, the boiler cycles around the minimum boiler set-

ting. This programmed function can be set to the OFF setting for con-

densing and electric boilers.

INSTALLATION:

Step One:

Check the contents of this package. If any of the contents listed are

missing  or  damaged,  please  contact  your  sales  representative  for

assistance. The SR501-OR includes:

SR501-OR Boiler Reset Control and Switching Relay Combination

One Outdoor Sensor

One Strap on Sensor

Instruction Sheet 

Replacement sensors are available from Taco, Inc.:

Strap on Sensor – 9300-2044RP

Outdoor Sensor – 9300-2052RP 

Note:

Carefully read the details of the Sequence of Operation section

in this brochure to ensure that you have chosen the proper control for

your application. 

Step Two:

Installing the Control:
The enclosure is to be mounted flush onto a wall or any ridge surface.

•   The mounting holes in the enclosure accept #6 screws. 

•   Line voltage to enter from bottom of control and low voltage to

enter from top of control.

Installing the Outdoor Sensor:

Note:

The temperature sensor (thermistor) is built into the enclosure.

•   Use one round or pan head screw to attach the base of the sen-

sor to the wall.

•   The sensor is wall mounted and the wiring enters through the

bottom of the enclosure. The hole for the cable entry must face

downward in order to prevent water from entering and filling the

enclosure.

CAUTION: Improper installation and operation of this control
could  result  in  damage  to  the  equipment  and  possibly  even
personal injury. It is your responsibility to ensure that this con-
trol  is  safely  installed  according  to  all  applicable  codes  and
standards. This electronic control is not intended for use as a
primary limit control. Other controls that are intended and cer-
tified as safety limits must be part of the control circuit. 

Summary of Contents for FuelMizer SR501-OR-4

Page 1: ...to the building The SR501 OR boiler reset control utilizes a reset ratio to set the relationship between outdoor tem perature and supply water temperature The reset ratio determines the amount the supply water temperature is raised for every 1 drop in out door air temperature and it is determined from the starting point and the system design conditions In order for the control to automatically det...

Page 2: ...er Shut Down WWSD When the outdoor temperature rises above 70 F 21 C the control turns off the boiler and blinks the Thermostat LED light This function only applies for space heating and does not affect DHW operation Boiler Operation When the SR501 OR has a reset demand the system supply water temperature is controlled by turning the boiler on and off The control calculates the target supply water...

Page 3: ... limit when there is a call for heat Boiler Minimum Supply Temperature Dip Switch 1 Most boilers require a minimum operating temperature to prevent cor rosion from flue gas condensation The minimum boiler dip switch should be set to ON 140 F supply water temperature so boiler can operate without causing the boiler flue gases to condense Consult the boiler manufacturer for recommended minimum boile...

Page 4: ...d and the read ings compared First measure the temperature using the thermometer and then measure the resistance of the sensor at the control The wires from the sensor must not be connected to the control while the test is performed Using the chart below estimate the temperature measured by the sensor The sensor and thermometer readings should be close If the test meter reads a very high resistanc...

Reviews: