(4) Connect the cables to inverter.
The power cables’ current capacity is 120Amps(peak).
If the battery system is supposed to configure with an inverter/charger
≥100Amps/2.5kW, must configure multiple pairs of external power cables following the
inverter/charger size.
Power Cable connection:
•
For 1 pair of external power cable, connect as A + D or B + C, donot connect as A+B or
C+D to avoid unbalancing current transmitted.
•
For 2 pairs of external power cable, connect as A + D and B + C.
•
For more than 2 pairs of external cable, need split the battery module into another string
to further handle the connection.
(5) There shall be a manual disconnecting device (breaker, etc.) between battery system
and inverter.