TA T011S User Manual Download Page 9

MOTOR

STANDARD

WORKING TIME

The opening and closing cycles are subdivided into two phases: The standard phase 

A1

 and the slowdown phase 

A2

.

A1

 

→ 

Programs the duration of the standard phase, during this time the force of the motor is 

A5

.

A2

 

→ 

Programs the duration of the slowdown phase, during this time the force of the motor is 

A6

.

The slowdown phase is performed after the standard phase.

A1

 →  

0.0 

to 

9.9

 and from 

10

 to 

99

 seconds.

A2

 →  

0.0 

to 

9.9

 and from 

10

 to 

99

 seconds.

A1

SLOWDOWN

WORKING TIME

A2

START UP TIME 

A3

 is the start up time of the motor. During this time the force of the motor increases 

constantly until it reaches the maximum power and the obstacle detection sensor is 
disabled. Each time the motor starts, the first 

A3

 seconds are the start up time. 

A3

 → 

0.1

 to 

1.5

 seconds. 

A3

STANDARD FORCE

A5

 is the force of the motor during the standard working time 

A1

. If 

A5

 increases, the 

sensitivity of the sensor decreases. If 

A5

 decreases, the sensitivity of the sensor increases. It 

is advisable to choose the required force of the motor first then calibrate the threshold 

A7

.

A5

 → 

3

 to 

10

A5

SLOWDOWN FORCE

A6

 is the force of the motor during the slowdown working time 

A2

. If 

A6

 increases, the 

sensitivity of the sensor decreases. If 

A6

 decreases, the sensitivity of the sensor increases. It 

is advisable to choose the required force of the motor first then calibrate the threshold 

A8

.

A6

 → 

6

 to 

10

A6

STANDARD OBSTACLE

DETECTION

THRESHOLD

This parameter will have effect during the standard working time 

A1

. If the control board 

detects a motor stress higher than 

A7

, it means that there is an obstacle in the way of the 

gate. The control board will make a decision in accordance with its programming as 
described in 

 SENSOR OPERATING MODE 

 (see page 7).

When the motor is on and the standard working time is in progress, the control board 
display shows the motor stress as number. You can use this value as a feedback value. 

00

 is 

the minimum and 

99

 is the maximum. The maximum value can be lower than 

99

. It 

depends on the motor. To disable the standard obstacle detection function set 

A7

 = 

no

To set 

no

 hold down or keep pressing button C until the display shows 

no

A7

 is settable

from 

00

 to 

99

. After 

99

 the control board display shows 

no

A7

 → 

00

 to 

99 

and 

99

 to 

no

 (DISABLED).  

A7

SLOWDOWN

OBSTACLE

DETECTION

THRESHOLD

This parameter will have effect during the slowdown working time 

A2

If the control board detects a motor stress higher than 

A8

, it means that there is an 

obstacle in the way of the gate.  The control board will make a decision in accordance with 
its programming as described in 

 SENSOR OPERATING MODE 

 (see page 7).

When the motor is on and the slowdown 

A2

 is in progress, the control board display 

shows the motor stress as a number. You can use this value as a feedback value. 

00

 is the 

minimum and 

99

 is the maximum. The maximum value can be lower than 

99

. It depends on 

the motor. To disable the slowdown obstacle detection function set 

A8

 = 

no

. To set 

no

 

hold down or keep pressing button C until the display shows 

no

A8

 is settable from 

00

 to

99

. After 

99

 the control board display shows 

no

A8

 → 

00

 to 

99 

and 

99

 to 

no

 (DISABLED).  

A8

www.tecnoautomazione.com

                                                                                                                                                                             

 

Pag. 7 / 17

Summary of Contents for T011S

Page 1: ...3DOLDQR 5 WDO RFDOLWj HUYLQDUD 7HO D 9LD 9LFLQDOH VQF LQIR WHFQRDXWRPD LRQH FRP ZZZ WHFQRDXWRPDWLRQ FRP 7 7HFQR XWRPD LRQH V U O A K M 7 W M J 7 M K A b M J 7HO HTSYWTQ ZSNY KTW XQNINSL LFYJX 86 5 0 1...

Page 2: ......

Page 3: ...E 6 A6 SLOWDOWN FORCE 6 A7 STANDARD OBSTACLE DETECTION THRESHOLD 6 A8 SLOWDOWN OBSTACLE DETECTION THRESHOLD 6 SENSOR OPERATING MODE 7 FUNCTIONS 8 F0 AUTO CLOSE TIME 8 F1 PEDESTRIAN WORKING TIME 8 F2 C...

Page 4: ...NTS A Button A B Button B C Button C D Button D F1 250 VAC power fuse 5A F4 Resettable fuse 24V 1 6A F5 Resettable fuse 24V 0 6A A B C Ground terminals CN Primary varistor V1 Secondary varistor V2 Ter...

Page 5: ...block input 7 is activated Parameter E7 is set to PE PEDESTRIAN A remote stored as r3 PEDESTRIAN START function is transmitting Eo DOMUS NO Terminal blocks inputs 1 2 3 4 or 7 are activated Parameters...

Page 6: ...INSTALLATION www tecnoautomazione com Pag 4 17 RADIO BODY BODY RADIO BASE LIGTHS max 10W 24V COVER COVER ANTENNA COVER ANTENNA BASE Screws and stops not included 3 5mm x 13mm 3 5mm x 13mm 4 mm x 35mm...

Page 7: ...VAC E1 DISABLED no START Go OPEN oP CLOSE CL E2 DISABLED no STOP 5t E5 DISABLED no CLOSING LIMIT SWITCH N C FC CLOSING LIMIT SWITCH N A LC E6 DISABLED no OPENING LIMIT SWITCH N C FA OPENING LIMIT SWIT...

Page 8: ...r remote key is activated when it is pushed down All these actions are recognized by the control board which shows these changes on the display When more inputs are activated at the same time the cont...

Page 9: ...dard working time A1 If the control board detects a motor stress higher than A7 it means that there is an obstacle in the way of the gate The control board will make a decision in accordance with its...

Page 10: ...detection mode If the opening limit switch input is not installed E6 no and the opening is in progress The sensor works in obstacle detection mode during the standard working time A1 During the slowd...

Page 11: ...t opening once the external photocells have been activated the gate will start to close after 5 seconds For safety reasons it is advisable to enable this function only when two pairs of external photo...

Page 12: ...ors are detected the motors can be started Vice versa the motors cannot start and the control board display shows 1t MOTORS TEST t2 t2 SI ENABLED t2 no DISABLED Before each gate movement the motor is...

Page 13: ...The motor works for a total time of A1 plus A2 seconds during the opening and the closing r2 STOP The stop function stops the gate r3 PEDESTRIAN The pedestrian function begins a Pedestrian Working Cyc...

Page 14: ...al photocells does not have any effect N C SAFETY DEF INTERNAL PHOTOCELL NC Go The START function begins a STANDARD WORKING CYCLE The gate opens for A1 plus A2 slowdown seconds stays open for F0 secon...

Page 15: ...To go to F0 press any start input F0 The pause time is being programmed F0 The gate is stopped The flashing lamp is on After 1 5 seconds the control board display shows the counting time To finish th...

Page 16: ...ivity The following tables show the values of A5 A6 A7 A8 B8 for electric gate motor models M2 500 M2 800 and M2 1500 www tecnoautomazione com Pag 14 17 STANDARD MODE SENSOR CALIBRATION ELECTRIC GATE...

Page 17: ...hts can be controlled by terminal block input remote key and or gate status The most useful functions are ON ON OFF ON from 0 to 99 Seconds Minutes Hours DOMUS controls up to 3 lights The lights can b...

Page 18: ...NOTES www tecnoautomazione com Pag 16 17...

Page 19: ......

Page 20: ...86 5 0 18 a 1 VHMS A 7b MJ 0 1 7 3DOLDQR 5 WDO RFDOLWj HUYLQDUD 7HO D 9LD 9LFLQDOH VQF LQIR WHFQRDXWRPD LRQH FRP ZZZ WHFQRDXWRPDWLRQ FRP 7 7HFQR XWRPD LRQH V U O A K M 7 W M J 7 M K A b M J 7HO J XMTU...

Reviews: