background image

Standby mode: 

This causes the actuator to close and turns the controller 
off, but it does leave the frost protection running. The 
pump exercise will also remain active.

Close Actuator: 

Forces the actuator to close or turns the boiler off.

Controller off :

Causes both actuator outputs to be off and stops the 
actuator.  In this mode no control function is operative
including frost protection and pump exercise.

Open Actuator: 

Forces the actuator to open or turns the boiler on.

6.2. REVIEW MODE

Review Mode is used to view parameters only, no settings can be changed in this
mode.  

The following parameters are available in Review Mode

Symbol

Description

Used In

Valve Opening

Review Mode

Valve Closing

Review Mode

Pump Running (CSC 5352 only)

Review Mode

Controller is in Night

Review Mode

Display Flow Temperature

Review Mode

Display Room Temperature or
Water Temperature for District Heating

Review Mode

Display Outside Temperature

Review Mode

Display Calculated Flow Set Value

Review Mode

Display Current Time and Day (CSC 5352 only) Review Mode

6.3. HOW TO ENTER QUICK SET MODE

1.

Press and hold the        

button

 and then the        

button

, keeping both buttons

pressed down until SEC appears on the display.  This means that mode
selection has been accessed.

2.

Press the        

‘tuning key’

 button followed by the        

‘enter’ button

 to access

the Quick Set Mode.

3.

The display will show the arrow pointing towards the         

‘tuning graphic’

 on

the left side of the display. 

CSC USER GUIDE

October, 03

33 of 42

Summary of Contents for Satchwell Climatronic CSC5252

Page 1: ...Satchwell Climatronic CSC5252 CSC5352 Compensator User s Guide SatchwellTM...

Page 2: ...pecial incidental or consequential damages arising out of purchase or use of this manual or the information contained herein Do not use the product for any other purposes than those indicated in this...

Page 3: ...3 DISTRICT HEATING SYSTEMS 16 3 3 1 Basic Wiring Diagram for District Heating Applications 18 3 4 ACTUATOR OVERRIDE FOR MAINS OUTPUT APPLICATIONS 19 3 5 ACTUATOR OVERRIDE FOR 24VAC OUTPUT APPLICATION...

Page 4: ...352 Only 30 5 SPECIFICATION 31 5 1 CHANGING THE BATTERY 32 6 FREQUENTLY USED FUNCTIONS AND USER SETTING RECORD TABLES 32 6 1 MANUAL OVERRIDES 32 6 2 REVIEW MODE 33 6 3 HOW TO ENTER QUICK SET MODE 33 6...

Page 5: ...l the output or flow temperature The temperature of the flow water is monitored to ensure that desired value is maintained to maximise energy savings The hot water can be supplied by a boiler or non s...

Page 6: ...tactors 2 2 WIRING PRECAUTIONS On new installations all sensor cables must be screened with the screens connected separately to the 0V earth point provided An MICC earth plate is provided for use if M...

Page 7: ...hange the CSC controllers programmed set point they fool the controller into believing that the space temp is above or below the ideal space temperature The CSC is primarily a water temperature contro...

Page 8: ...ime clock See the Quick Set mode for details on setting the clock 8 Complete the configuration via the Quick Set and Fine Tune parameters Which Parameters to Change The CSC is programmed with typical...

Page 9: ...you have a Space Sensor what will be your target Space temperature for the Day Period SVn Set Value Night Origin If you have a Space Sensor what will be your target Space temperature for the Night Pe...

Page 10: ...and control to the NSB requirement During the event of frost out of hours the controller will display Auto 1 to indicate that the controller is working correctly Low Flow Temperature Stage Two Frost...

Page 11: ...ntrol loop stability at frequent intervals as a part of an on going maintenance program This will ensure maximum energy savings and component life Flow High Limit Depending on your application it may...

Page 12: ...to 1 is displayed on the controller The CSC will resume normal operation when the outside temperature increases by 2 C If a space sensor is used then this will also provide frost protection to protect...

Page 13: ...nd or Night Set Back is used Set Up Boost Night Set Back Pump Time switch version only 230Vac Actuator ARM Mk 2 Actuator 1 Red 2 Blue 3 Black Links 7 8 and or 9 10 must be removed if Set up and or Nig...

Page 14: ...o 1 is displayed on the controller The CSC will resume normal operation when the outside temperature increases by 2 C If a space sensor is used then this will also provide frost protection to protect...

Page 15: ...p and or Night Set Back is used Set Up Boost Night Set Back Pump Time switch version only 230Vac Boiler Output Boiler Links 7 8 and or 9 10 must be removed if Set up and or Night Set Back is used Set...

Page 16: ...hours if the outside temperature drops below an adjustable frost setting defaulted to 0 C the pump is enabled and Auto 1 is displayed on the controller The CSC will resume normal operation when the o...

Page 17: ...r controlling primary water temperature in Scandinavian Public Systems Pump Time switch version only Optional Flow Temp Boiler Fig 7 A safety high thermostat may need to be used on the secondary side...

Page 18: ...nly Links 7 8 and or 9 10 must be removed if Set up and or Night Set Back is used Set Up Boost Night Set Back Pump Clock Version only 230Vac Boiler Output Links 7 8 and or 9 10 must be removed if Set...

Page 19: ...ride that was used Override Open Override Close Single pole relay or contact Single pole relay or contact Fig 10 Open Close Open Close When upgrading an old CSC or CSC this method reproduces the 4 5 l...

Page 20: ...tton Selects the mode that allows setting of the Time Switch functions Tuning Button Selects the mode that allows setting of the controller parameters Enter Button Enter button for confirming the entr...

Page 21: ...of the set parameters Day mode Removes the effect of the time schedule and makes the controller run at the day set value constantly Night mode This mode overrides the controller time schedule and dec...

Page 22: ...y 08 00 00 00 00 00 17 00 3 Wednesday 08 00 00 00 00 00 17 00 4 Thursday 08 00 00 00 00 00 17 00 5 Friday 08 00 00 00 00 00 17 00 6 Saturday 00 00 00 00 00 00 00 00 7 Sunday 00 00 00 00 00 00 00 00 Pl...

Page 23: ...de It shows various temperatures the status of the actuator pump and the current time and day No settings can be changed in this mode except the facilities on the manual override switch The main displ...

Page 24: ...ymbol Description Used In Default Range Tuning Key Indicates that you are in Quick Set Mode if the arrow is lit Quick Set Mode Set Current Time and Date CSC 5352 only Quick Set Mode 00 00 to 23 59 1 t...

Page 25: ...his ratio is used between the Changeover point Co and the flow high limit setting The value set is divided by 10 to get the actual ratio E g 30 is equivalent to a ratio of 3 1 Quick Set Mode 30 3 1 0...

Page 26: ...er 1 to 7 with 1 representing Monday and 7 representing Sunday If you decide not to change the value at any stage press the tuning button instead 4 Press the enter button to enter the day number and t...

Page 27: ...ne Mode at any time press the tuning key button If no keys are pressed within a period of 30 seconds then the product will return to the Review mode The user parameters that can be viewed and or adjus...

Page 28: ...can be manually set if required Fine Tune Mode 5 1 or 5 Sensor Averaging This tells the CSC how many Room Sensors are connected to it Averaging Fine Tune Mode 1 1 to 4 Set Boiler Hysteresis Sets the...

Page 29: ...nt the heating will come on in boost until the hysteresis 2 C has been cleared If an adjustable room sensor is used then this setting must be set to 10 C to remove frost protection Failure to do so ma...

Page 30: ...used for the Max Return Ratio setting e g 83 0 83 Fine Tune Mode 83 10 to 127 4 5 2 To Adjust the Economy Mode CSC 5352 Only Economy mode is used to override the plant in the event of a high outside t...

Page 31: ...2 5mm2 cross section Protection Class IP 30 Case Matt black coloured 2 piece polycarbonate case Fire resistant to UL94V 0 Mounting Wall or panel mounting Case Dimensions 144 x 144 x 136mm Panel Cut O...

Page 32: ...CH BACK TO AUTO AFTER THE MANUAL OVERRIDE FUNCTION HAS BEEN USED WHEN THE SWITCH IS IN AN OVERRIDE CONDITION THE DISPLAY WILL FLASH AND THE OVERRIDE CONDITION WILL BE INDICATED EXCEPT IF IT IS OVERRID...

Page 33: ...l Description Used In Valve Opening Review Mode Valve Closing Review Mode Pump Running CSC 5352 only Review Mode Controller is in Night Review Mode Display Flow Temperature Review Mode Display Room Te...

Page 34: ...lue Sets the amount the flow temperature should be increased by during set up Quick Set Mode 10 0 to 255 C Set Flow High Limit Temperature The highest controlled flow temp used Quick Set Mode 82 0 to...

Page 35: ...falls below the economy set value within 1 hour of the end of occupancy time the controller will remain in economy mode 1 Make sure that you are in Fine Tune mode 2 Use the and buttons to obtain the e...

Page 36: ...n a continuous demand signal Fine Tune Mode 120 0 to 999 PB Controller Tuning C Used to tune the controller to the control system Fine Tune Mode 50 0 to 255 Select NSB action CSC 5352 only Setting thi...

Page 37: ...CSC how many Room Sensors are connected to it Averaging Fine Tune Mode 1 1 to 4 Set Boiler Hysteresis Sets the number of C the actual flow temperature must be above the calculated flow temperature bef...

Page 38: ...start the pump and control the valve boiler to the NSB setting until the Hysteresis 2 C outside has been cleared Fine Tune Mode 1 0 UK 1 European Low Space Temperature Setting CSC 5352 only if space s...

Page 39: ...in Only used when a space temperature sensor is fitted The space temperature will influence the compensated flow temperature for each C error from this figure Subject to the fine tune setting INF or I...

Page 40: ...00 2 Tuesday 08 00 00 00 00 00 17 00 3 Wednesday 08 00 00 00 00 00 17 00 4 Thursday 08 00 00 00 00 00 17 00 5 Friday 08 00 00 00 00 00 17 00 6 Saturday 00 00 00 00 00 00 00 00 7 Sunday 00 00 00 00 00...

Page 41: ...CSC USER GUIDE October 03 41 of 42...

Page 42: ...February 08 CSC USER GUIDE 42 of 42 S317856100_A5...

Page 43: ......

Page 44: ...741100 satchwell info uk tac com www tac com Copyright 2008 TAC All brand name trademarks and registered trademarks are the property of their respective owners Information contained within this docum...

Reviews: