The controller functions available for viewing in Review Mode are as follows:
4.4. ACCESSING AND EXITING QUICK SET MODE
1.
Press and hold the
button
and then the
button
, keeping both buttons
pressed down until SEC appears on the display. This means that mode
selection has been accessed.
2.
Press the
‘tuning key’
button
followed by the
‘enter’ button
to
access the Quick Set Mode.
3.
The display will show the arrow pointing towards the
‘tuning graphic’
on
the left side of the display.
4.
To exit Quick-Set the
‘tuning key’ button
must be pressed when the icons
are flashing. If no keys are pressed within 30 seconds the controller will return
to the default review mode.
The user settings that are able to be adjusted or viewed in the Quick Set Mode are:
Symbol Description
Used In
Default Range
Tuning Key
Indicates that you are in Quick Set Mode if
the arrow is lit
.
Quick Set
Mode
–
–
Set Current Time and Date
(CSC 5352 only)
Quick Set
Mode
–
00:00 to
23:59
1 to 7
r
1
Set Compensator Ratio 1
Used to set the compensation ratio. E.g.
30 equals a ratio of 3:1.
Quick Set
Mode
25
(2.5:1)
0 to 255
Set Night Set Back Value (NSB)
Sets the amount the flow temperature
should be decreased by during NSB.
Quick Set
Mode
10
0 to
255
°
C
Set Flow Temperature Set Up Value
Sets the amount the flow temperature
should be increased by during set up.
Quick Set
Mode
10
0 to
255
°
C
Symbol
Description
Valve Opening
Valve Closing
Pump Running
(CSC 5352 Only)
Controller is in
Night
Display Flow
Temperature
Symbol
Description
Display Room Temperature
Display Outside
Temperature/Water
Temperature for District
Heating
Display Calculated Flow Set
Value
Display Current time and
Day (CSC 5352 Only)
August
, 0
7