background image

F-24853-4

©

 

Copyright 2006 TAC All Rights Reserved.

3

Programming information is contained in this document. For 
further details regarding software configuration, please refer 
to the appropriate User’s Guide and the TAC MicroSmart 
Operator Interface User’s Guide.

Included in This Package

The MPC-8AI is supplied with:

1. One N1-1092 MPC-8AI module circuit board.

2. Two 8-pin connectors (green, N100-410659), for 

connection to analog inputs AI1-AI8.

Other Components

The MPC-8AI requires direct connection to a TAC MicroSmart 
MSC-MPC Multi-purpose controller.

Options and Accessories

TS-5800 and TS-58000 series platinum RTD room 
thermostats and remote sensors, and TS-8100 and TS-81000 
series Balco sensors. See separate platinum RTD room 
sensor data sheet for special models using RJ-11 jacks, 
adjustable setpoints, and pushbutton/LED overrides.

Power Requirements

The MPC-8AI is powered on when connected to a functional 
MSC-MPC. No additional power is required.

Caution:

Disconnect power supply from associated MSC-

MPC controller before installing MPC-8AI to prevent electrical 
shock and equipment.
More than one disconnect switch may be required to de-
energize this equipment before servicing.
Do not attempt to power the unit ON until installation is 
complete.

Installation

The MPC-8AI is a module that fits into any of the four option 
slots on the MSC-MPC. To install, remove power from the 
MSC-MPC and insert the MPC-8AI into the desired option slot 
on the MSC-MPC. Wiring instructions, diagrams, and 
software assignments are provided below.

Note: When installing the MPC-8AI, be sure that the 
controller is fully seated to the backplate before and after the 
backplate is fastened to the enclosure.

Sensor Grounding

The shield wire for the room sensor should be grounded to 
chassis where the wire enters the enclosure. This ensures 
maximum protection from electrical noise and electrostatic 
discharge.

Wiring Instructions and Setup Information

Temperature Sensing Inputs

The MPC-8AI allows two types of analog inputs for the 
purpose of temperature sensing. They are:

– 1000 ohm platinum RTDs (-40 to +240 °F)
– 1000 ohm Balco RTDs (-30 to +240 °F)

Note: T99 Series temperature sensors cannot be used with 
the MPC-8AI module.

Platinum RTD Inputs

The inputs provided for these sensors are terminals AI1 A&B 
through AI8 A&B. The inputs are two-wire, twisted pair with 
shield.

Inputs are not polarized, terminate one of the wires to terminal 
A and the other wire to terminal B. Terminate the shield to 
cabinet ground closest to the entry point of the wire into the 
enclosure (cut off all additional wire). Cut and tape the shield 
at the sensor end to prevent it from coming in contact with 
junction box or other conductors. Refer below for wiring and 
setup information.

Figure-2 Platinum RTD or Balco Resistance Temperature 

Sensor.

Table-1 illustrates the numbering scheme and software 
assignments of the platinum RTD inputs. When making these 
assignments, the first entry is the option slot number on the 
connected MSC-MPC controller and the second entry is the 
number of the analog input being using.

For example, when plugged into option slot number 2, analog 
input number 1 has an assignment of AI 21.

Summary of Contents for MPC-8AI

Page 1: ...C to 115 C 0 06 C resolution 0 11 Vdc 0 005 volt resolution 4 20 mA 0 01 mA resolution Contact Inputs Used for status monitoring of dry contacts Operating Environment 32 to 122 F 0 to 50 C 5 85 RH non...

Page 2: ...2 Copyright 2006 TAC All Rights Reserved F 24853 4 Figure 1 TAC MicroSmart MPC 8AI Analog Input Module...

Page 3: ...rams and software assignments are provided below Note When installing the MPC 8AI be sure that the controller is fully seated to the backplate before and after the backplate is fastened to the enclosu...

Page 4: ...g the element OFSET simply subtract 77 from the value given in the table for OFSET 0 11 Vdc Analog Inputs When configured as a voltage sensor input the universal analog input measures between 0 and 11...

Page 5: ...percent open For the point to be calibrated set OFSET 0 and SCALE 4096 With the feedback wired drive the actuator valve fully open 100 Record the measured bit value displayed by the system for this p...

Page 6: ...rmally closed contact input excluding pulse inputs This input utilizes a 1K ohm 1 1 4 watt supervision resistor installed with the input device The device is terminated to the appropriate AI connector...

Page 7: ...e assignment required for the corresponding hardware address of the selected contact input is shown in Table 5 below Table 5 Assignments for AIs used as Normally Closed Contact Inputs INPNT AI as show...

Page 8: ...marks and registered trademarks are the property of their respective owners Information contained within this document is subject to change without notice F 24853 4 www tac com TAC 1354 Clifford Avenu...

Reviews: