FCU2001 and SY100 Engineering Guide     

9

 

 

 

 
 

Chapter 3 
Programming of the FCU2001 

Once power has been supplied to the controller it will need to be programmed. This is carried out 
via the SY100 interface  
 

• 

Sop the Fan-coil by means of the On/Off button.  

• 

Pess the button marked with a Fan then jointly press the On/Off button simultaneously, hold for 

3 seconds. 

PROGRAMMING OF THE ADDRESS OF THE CONTROLLER 

 
The assigned number of the controller will be displayed. 
 
Pressing On/Off we will happen to modify the units. This will be marked appearing the point decimal 
on them. With /- we can increment/decrement the units until the required number is shown.  
 
If you are happy with the number set the press “On/Off” again to store this first value.  
 
If you wish to change to “tens” press the Fan button once more. 
 
In the tens range we will have the same procedure, only that the decimal point will be located in this 
area. In order to change to hundreds press the “Fan” button and the to finish press “On/Off”. 
 
In the hundreds exactly the same. With the Fan button we will enter again to the units and we will 
finish with On/Off. 
 

PROGRAMMING OF THE REST OF PARAMETERS 

 
 
Unlike the address of the controller, the rest of parameters that establish the way of operation of 
FCU 2001, only can take values “N2 (No) or “S” (Set) and the programming style is similar to the 
one previously described for the address.  
 
10 programmable parameters exist, P-0 to P-9 whose meaning is detailed in the attached table. 
 

 

Program Description. 

Default. 

Value 

 

 

Controller Bus Address 

001 

001 

P0 

Type of application, 2 or 4 pipe 

2 tubes 

P1 

Summer/Winter or by entrance. 

According to P7 

P2 

Limited set point. 

Limited. 

P3 

Operation in Standby. 

Off 

P4 

Minimum speed in automatic. 

No fan. 

P5 

Control of Presence. 

Room Key Socket 

P6 

Hidden temperature on SY display 

Visible  temperature  on 
SY display 

P7 

State of Winter, single if P1 = N 

Summer. 

P8 

Contact of window 

No .not used 

P9 

Contact bathroom alarm 

No .not used 

 

P0.- N=2 pipe ; S=4 pipe 
P1.- N=P7 ; S= Entrance 

Summary of Contents for FCU2001

Page 1: ...FCU2001 and SY100 Digital Interface Engineering Guide Copyright 2004 Syxthsense Ltd All rights reserved...

Page 2: ...this document in good faith based on information made available to it by third party contributors SyxthSense reserves the right to make amendments and to correct any errors that are identified herein...

Page 3: ...MODE 7 INTRUDER ALARMS 7 ALARM OF OPEN WINDOW 7 BATHROOM ALARM 8 CHAPTER 3 PROGRAMMING OF THE FCU2001 9 PROGRAMMING OF THE ADDRESS OF THE CONTROLLER 9 PROGRAMMING OF THE REST OF PARAMETERS 9 THE CONT...

Page 4: ...n electrical enclosure or on the Fan coil unit itself adjaecent to the power supply and valve connections The FCU 2001 can be stand alone with a display or it can be networked to a central BMS system...

Page 5: ...ler CONTROLLING THE TEMPERATURE The FCU 2001 measures the room temperature by means of the sensor located in the return duct of the Fan coil Based on this temperature the controller will enable the ap...

Page 6: ...ting valve and it will remain open until the temperature reaches the set point again At the same time the fan will start up according to the previously described mode of operation The valve behaviour...

Page 7: ...oning working etc the setpoint can be controlled from the BMS to place greater influence over the setpoint more so than can be achieved via the local interface The BMS can force the controller into a...

Page 8: ...LARM The bathroom alarm will activate independent of the state of the Fan coil The activation of the contact will raise the alarm This information will stay until we remove the indication by communica...

Page 9: ...ly that the decimal point will be located in this area In order to change to hundreds press the Fan button and the to finish press On Off In the hundreds exactly the same With the Fan button we will e...

Page 10: ...ed to send a generic message Broadcast to all of the controllers Therefore the units begin in 001 3 This data could not be changed by communications 4 By hardware considerations we have a commitment b...

Page 11: ...e the heating when leaving the room and in winter it would activate the conditioned air The value of the increments reduction can be modified voluntarily through the Bus of Communication being a value...

Page 12: ...to avoid this maneuver we have this program Value N defines that we do not need this contact Annulling the functions associated the window It is the value by default Value S considers that if we need...

Page 13: ...l have a 1 in display of the Fan coil If the entrance is not active we will have a 0 E3 The E3 input is assigned to the Window Opening the window we will have a 1 in display of the Fan coil If the ent...

Page 14: ...yxthSense Limited Gibbs House Kennel Ride Ascot SL5 7NT United Kingdom Enquiries T 0870 20 80 100 F 0870 20 80 200 Online store www syxthsense com Copyright 2004 SyxthSense Limited All rights reserved...

Reviews: